4.5
–
Jockey Limit Reset
If the pump has entered jockey mode five times or more within a week then the ‘Jockey
Limit’ fault will be displayed, this may also be displayed shortly after start
-up/initial filling
of the system.
To reset the ‘Jockey Limit’ initiate a weekly test proced
ure by following
the steps in 5.3.
4.6
–
Pump Running Indicator
A ‘Pump Running’ fault will be displayed If the fire sprinkler pump was to run for more
than one minute, this is to meet the requirements of BS9251:2021 to ensure in the event
of a fault whereby the pump was running when not called upon then a fault signal is
transmitted. Note: This fault will be present when operating the pump set in ‘Fire Mode’
for more than one minute, this will reset automatically when stopped.
4.7
–
Internal Audible Alarm (Optional)
The optional internal audible alarm powered by a 9v battery will make an audible bleep
when any fault condition arises including power failure to the pump controller. This
audible alarm should be requested where the standard fault output contacts cannot be
monitored. Note: Selecting internal audible alarm option will as standard remove the
fault output contacts.
Supplied 9v battery to be inserted into the battery carrier on the underside of the
controller.