Aquaguard BS925 2021 User & Installation Manual Download Page 5

Page | 5  

 

 

3. Installation Guide 

 

General 

3.1 - This product must be installed by a suitably qualified electrician.  

3.2 - This controller must be earthed. 

3.3 

 This controller should be wired to a suitable isolator, fed directly from the electrical 

distribution board protected by a dedicated RCD/RCBO suitably sized for the fire pump 
installed. 

Installation 

3.4 

 If purchasing in kit form the AquaGuard Fire Pump Controller must be connected as 

per diagram below. Take care with solenoid connection as 230v will be present to 
solenoid when requested. 

 

 

Fig.1 

Summary of Contents for BS925 2021

Page 1: ...Page 1 AquaGuard BS9251 2021 Fire Pump Controller User Installation Manual...

Page 2: ...allation Guide Page 5 4 Controller Set Up and User Guide Page 6 8 5 Commissioning Page 9 6 Annual Maintenance Page 10 7 Fault Alarm Table Page 11 8 Troubleshooting Page 12 13 If additional assistance...

Page 3: ...ly limit Fire Mode If pressure loss and flow are detected by either of the two pressure switches and the flow switch then pump will operate in fire mode until manually shut down Test Mode Each Monday...

Page 4: ...Page 4 2 User Interface 2 1 AquaGuard fire pump controller button and LED description 2 2 AquaGuard fire pump controller LCD Display Home Screen description Controller Home Screen...

Page 5: ...be wired to a suitable isolator fed directly from the electrical distribution board protected by a dedicated RCD RCBO suitably sized for the fire pump installed Installation 3 4 If purchasing in kit f...

Page 6: ...ll volume in the pump manifold Warning Tank must be full pump must be fully primed from all bleed nipples and all suction valves must be open prior to powering the controller up for the first time 4 2...

Page 7: ...con enter the user password 2000 press right to the key symbol then press ok tick Note Access to the setup menu is possible by entering an advanced password but the installer will be required to speak...

Page 8: ...ult whereby the pump was running when not called upon then a fault signal is transmitted Note This fault will be present when operating the pump set in Fire Mode for more than one minute this will res...

Page 9: ...hat the pressure switches are set within 0 3 bar of each other Refer to pressure switch instruction manual for setting instructions this should be undertaken with the Aquaguard pump controller switche...

Page 10: ...ion 4 4 enter main menu navigate to the Enter password section enter code 2000 then press ok on the key symbol 3 Enter main menu navigate to the Commands menu while holding the Manual mode button pres...

Page 11: ...Page 11 8 Fault Alarm Table If any faults are present on the controller then these will be displayed on the LCD display with a code A01 A38 or UA1 8 see alarm table below for description...

Page 12: ...ssure low or at zero Pressure switches not wired correctly or pressure switch setting too low Pressure switch cable wired to flow switch Wire pressure switches between COM and 1 normally closed Set co...

Page 13: ...e if necessary Fault present on pump controller Refer to fault alarm table in section 8 to identify fault and possible action required Undertake action if possible Call Aquaguard if problem persists P...

Reviews: