2.5 Water Flow Rates
Maintain water flow rates as indicated. Please note, these specifications relate to the chiller only. Code-
specified whole system turnover rates must be satisfied.
NOTICE
Failure to heed the following may result in damage to equipment.
l
Water flow exceeding maximum flow rates will negatively affect the total pool
filtration performance and may damage the chiller. This will not be covered under
equipment warranty.
MODEL
HEAT EXCHANGER TYPE
FLOW RATES
MINIMUM MAXIMUM
TC500
Titanium Tube-in-Tube
20 GPM
45 GPM
TC1000
Titanium ThermoLink
®
30 GPM
70 GPM
PLEASE NOTE -
If minimum flow rates are not met, chiller performance is reduced and performance will
suffer. Internal safety devices may deactivate the chiller with the following errors:
l
HP
and
HP5
l
or (if equipped) error codes of
LP
and
LP5
l
Operate water filtration devices per manufacturer's specifications. Dirty filters can cause a reduction of water flow
to the chiller. An increase of 7-10 psi higher than the clean filter pressure typically reduces flow rates. This
requires the filter to be cleaned or back-washed.
l
Keep baskets free of debris. A large quantity of debris in the pump and skimmer baskets can reduce water flow.
l
Check for improper valve settings. A partially closed valve after the filter, or a full-open bypass around the
chiller, will cause insufficient water flow through the chiller.
l
The maximum static pressure (or operating pressure) is 50 pounds-per-square-inch (PSI). These specifications
relate to the chiller only.
l
Code-specified whole system turnover rates must be satisfied.
2.6 Adjusting Water Flow Using ΔT (Delta-T)
The Delta-T is the temperature difference between the water temperatures entering and leaving the chiller. The
equipment can be fine-tuned for maximum performance by balancing water flow rates to maintain an ideal
∆T.
l
Installed temperature ports are required to perform the following procedures.
l
This adjustment procedure must be completed with the unit in heating mode
.
PLEASE NOTE -
l
The installation of temperature ports are required for all commercial applications.
l
The installation of temperature ports are strongly recommended for residential installations.
l
See "Temperature Port Kit" on page 19.