Page - 70
MULTI-UNIT COMM FAULT
ISSUE
Slaved heat pump is not receiving a signal from the master heat pump.
RESOLUTION
1. Confirm the master heat pump is operating correctly. If, for example, no power is supplied to the master
heat pump, an error will appear on the slaved heat pumps.
2. Confirm the heat pump is properly connected and configured to a master unit.
l
Connecting Multiple Heat Pumps (Master / Slaved)
OTA SYSTEM LOCKOUT
ISSUE
A malfunction has occurred that could allow the water temperature to surpass a safe level. An installed
"Over Temperature Alarm" kit has disabled the system.
l
" on page 83 for more information.
RESOLUTION
Call for service.
SMART COMM FAULT
ISSUE
Heat Pump is not receiving a signal from an external controller using a smart bus connection point.
RESOLUTION
1. Confirm a smart bus external controller is being used.
l
If not, set external controller mode to "none" instead of "SMART".
o
Configure for Smart Bus Controller
2. Confirm connection points from the external controller to the heat pump are correctly configured.
l
Connecting Smart Bus Controllers
3. If using a smart bus external controller, confirm the controller is correctly set to send signals to the heat
pump. See manuals or guides provided with the external controller.
VARIABLE DRIVE FAULT
ISSUE
A problem was detected in the variable speed compressor.
RESOLUTION
Deactivate heat pump at power disconnect. Wait for two minutes for the capacitors to discharge.
Then reactivate heat pump's power at disconnect. If error reoccurs, call for service.
WATER TEMP SENSOR SHORT
or
WATER TEMP SENSOR OPEN
ISSUE
Shorted or open water sensor.
RESOLUTION
A qualified technician should replace the water sensor.
2
-
T
roubl
es
hoot
ing
Summary of Contents for HeatWave SuperQuiet SQ120R
Page 2: ......
Page 28: ...Page 24 Configure Call Flex Enter Installer Menus then proceed 1 Installation ...
Page 33: ...Page 29 Configure for Smart Bus Controller Enter Installer Menus then proceed 1 Installation ...
Page 36: ...Page 32 Configure 2 wire controller Enter Installer Menus then proceed 1 Installation ...
Page 40: ...Page 36 1 Installation ...
Page 41: ...Page 37 Configure for Scheduled Mode Enter Installer Menus then proceed 1 Installation ...
Page 42: ...Page 38 1 Installation ...
Page 45: ...Page 41 1 Installation ...
Page 47: ...Page 43 1 Installation ...
Page 50: ...Page 46 1 Installation ...
Page 53: ...Page 49 1 Installation ...
Page 55: ...Page 51 1 Installation ...
Page 58: ...Page 54 Turbo Boost 1 Installation ...
Page 59: ...Page 55 Set Efficiency Mode to 24 Hour 1 Installation ...
Page 60: ...Page 56 Set Efficiency Mode to Filtration Schedule 1 Installation ...
Page 61: ...Page 57 1 Installation ...
Page 63: ...Page 59 1 Installation ...
Page 65: ...Page 61 1 Installation ...
Page 84: ...Page 80 Model Number Example 3 Appendix ...
Page 89: ......
Page 144: ...Rev L 8 12 13 MASTERTEMP Pool and Spa Heater Installation and User s Guide 55 N TES ...