1.6.e Connecting Multiple Heat Pumps (Master / Slaved)
Up to 16 heat pumps can be connected and controlled from a primary heat pump.
There are two reasons for using a multiple heat pump configuration:
1. Controlling multiple heat pumps from one location; the master heat pump.
2. Preventing heat pumps from starting up at the same time and causing an excessive power draw
on the electric circuit.
DANGER
Failure to heed the following will result in injury or death.
l
RISK OF ELECTRICAL SHOCK FROM ENERGY STORED IN CAPACITORS - MODELS EQUIPPED
WITH VARIABLE FREQUENCY COMPRESSOR DRIVES STORE ELECTRICITY EVEN AFTER THE
POWER HAS BEEN DEACTIVATED AT THE POWER BREAKER.
Wait for 2 minutes after the shut down
of equipment before servicing.
l
Deactivate power while routing wiring to control board.
l
Follow all National Electric Codes (NEC) and/or State and Local guidelines.
WARNING
Failure to heed the following may result in injury or death.
l
This section is only for qualified installers who are familiar with the swimming pool and spa safety standards.
l
The installer must be familiar with service industry techniques.
NOTICE
Failure to heed the following may result in damage to equipment.
l
The wire size connecting the heat pumps must be 22-gauge, 2-conductor,
low-voltage wire. Be sure that the size of the wire will allow at least two
wires per connection point.
l
Do not attempt to connect heat pump equipment in multiple configurations
with previous HP7 and HP7R versions of the microprocessor. See
No onboard port is provided for heat pumps with these microprocessor
versions. An Automatic Sequencing Controller (ASC) accessory is required
for those types of heat pumps.
DO NOT CONNECT
HP7 or HP7R boards
Figure 7
Connecting Multiple Heat Pumps
Dry Contact Connection
Points to the Microprocessor
Figure 8
1. Choose one unit to be the lead (or master) unit. This is typically a
unit that can be accessed easily when temperature adjustments are
needed.
l
Note - The Lead unit can be connected to an external controller
via the "smart bus" connection point if desired.
2. Deactivate power to heat pumps.
3. Remove electrical access panels.
4. Route 22-gauge, 2-conductor, low-voltage wires to the low voltage
sides of the electrical enclosures. Follow all National Electric Codes
(NEC) and/or State and Local guidelines.
5. Connect the first slaved heat pump's wires to the unit selected as the
master heat pump's.
1
-
Ins
ta
lla
tion
Summary of Contents for HeatWave SuperQuiet SQ120R
Page 2: ......
Page 28: ...Page 24 Configure Call Flex Enter Installer Menus then proceed 1 Installation ...
Page 33: ...Page 29 Configure for Smart Bus Controller Enter Installer Menus then proceed 1 Installation ...
Page 36: ...Page 32 Configure 2 wire controller Enter Installer Menus then proceed 1 Installation ...
Page 40: ...Page 36 1 Installation ...
Page 41: ...Page 37 Configure for Scheduled Mode Enter Installer Menus then proceed 1 Installation ...
Page 42: ...Page 38 1 Installation ...
Page 45: ...Page 41 1 Installation ...
Page 47: ...Page 43 1 Installation ...
Page 50: ...Page 46 1 Installation ...
Page 53: ...Page 49 1 Installation ...
Page 55: ...Page 51 1 Installation ...
Page 58: ...Page 54 Turbo Boost 1 Installation ...
Page 59: ...Page 55 Set Efficiency Mode to 24 Hour 1 Installation ...
Page 60: ...Page 56 Set Efficiency Mode to Filtration Schedule 1 Installation ...
Page 61: ...Page 57 1 Installation ...
Page 63: ...Page 59 1 Installation ...
Page 65: ...Page 61 1 Installation ...
Page 84: ...Page 80 Model Number Example 3 Appendix ...
Page 89: ......
Page 144: ...Rev L 8 12 13 MASTERTEMP Pool and Spa Heater Installation and User s Guide 55 N TES ...