 WARNING: Important Notes for Plumber 

 

The solar hot and solar cold pipe work between the storage cylinder and the solar collectors and the 
pipe  work  between  this  solar  water  heater  and  a  temperature  limiting  device,  or  this  solar  water 
heater and a hot water outlet if a temperature limiting device is not installed 

MUST BE

 of copper. All 

compression fittings must use brass or copper olives. 

 

The full length of the solar hot and solar cold pipes 

MUST BE

 insulated. 

The insulation must; 

 

be of a closed cell type or equivalent, suitable for a solar water heating application and capable 
of withstanding the temperature of the water generated by the solar collectors under stagnation 
conditions which may be up to 150°C. The specification of the chosen insulation material should 
be checked with the insulation manufacturer prior to installation as different materials may  vary 
in temperature tolerance. 

 

be  at  least  13 mm  thick,  however  thicker  insulation  may  be  required  to  comply  with  the 
requirements of AS/NZS 3500.4. 

 

be weatherproof and UV resistant if exposed. 

 

extend through any penetrations in the eaves, ceiling and roof. 

 

cover valves and fittings in the solar hot and solar cold pipe work. 

 

be  fitted  up  to  and  cover  the  connections  on  both  the  solar  storage  cylinder  and  the  solar 
collectors. 

Note: Failure to observe these requirements increases the risk of freeze damage. 

Uninsulated  pipe  work,  including  uninsulated  pipe  work  concealed  in  cavities  and  roof  spaces  or 
where  it  may  be  in  contact  with  a  metal  roof,  may  lead  to  freeze  damage.  The  system  has  NO 
WARRANTY for freeze damage if the solar hot and solar cold pipes are  not insulated in accordance 
with the installation instructions. 

Pipe work insulation is essential to assist in; 

 

providing freeze protection. 

 

providing corrosion protection to a metal roof from water runoff over the copper pipe. 

 

avoiding  accidental  contact  with  the  solar  pipe  work  which  can  become  very  hot  as  high 
temperature water can flow from the solar collectors to the solar storage cylinder. 

 

reducing pipe heat losses. 

The insulated copper pipe work; 

 

should  be  fixed  at  suitable  locations  to  prevent  or  reduce  the  possibility  of  noise  from  water 
hammer and vibration from occurring. 

 

is not to be placed or installed in contact with plastic pipe work. 

Likewise,  plastic  pipe  work  is  not  to  be  placed  or  installed  in  contact  with  the  insulated  copper 
pipe work after the solar circuit is installed. 

 

Plastic pipe 

MUST NOT

 be used, as it will not withstand the temperature and pressure of the water 

generated  by  the  solar  collectors  under  stagnation  conditions.  The  solar  collectors  can  generate 
extremely  high  water  temperatures  up  to  150°C  and  high  water  pressure  of  1000 kPa.  Plastic  pipe 
cannot withstand these temperatures and pressures and 

MUST NOT

 be used. Failure of plastic pipe 

can lead to the release of high temperature water and cause severe water damage and flooding. 

 

The highest point of the solar cold pipe and solar hot pipe must be where they connect to the solar 
collectors, to avoid the possibility of air locks occurring in the system. There 

must be a continuous 

fall

 in the pipe work between the solar collectors and solar storage cylinder. Horizontal runs of pipe 

work are acceptable and may be installed. 

 

A non return valve 

MUST BE

 installed on the cold water line to the solar storage cylinder 

AFTER

 the 

cold  water  branch  to  a  temperature  limiting  device.  Due  to  the  high  water  temperatures  generated 
under certain conditions in the solar collectors of this solar water heater, an additional effective back-
flow  prevention  device  also  should  be  used  as  an  extra  safeguard.  Valve  manufacturer  RMC 
recommends Dual Check Valve model N7150, as being suitable for this application. 

 

The  pressure  applied  to  the  solar  circuit  and  solar  collectors  during  a  pressure  test 

MUST NOT

 

exceed 1000 kPa, otherwise damage may result to the solar collectors.  

Summary of Contents for SG165 Series

Page 1: ...165 to SG415 Series Warning Use copper pipe ONLY Plastic pipe MUST NOT be used It is a requirement of a solar water heater installation that all pipe work be in copper and not plastic due to the effec...

Page 2: ...r water heater is turned on Patents This solar water heater may be protected by one or more patents or registered designs in the name of Aquamax Australia Pty Ltd or Rheem Australia Pty Ltd Trade Mark...

Page 3: ...6 Gas Booster Installation 17 Solar Controller Kit Installation 18 Solar Collector Kit Installation 18 INSTALLATION PLUMBING PLUMBING CONNECTIONS 20 Solar Storage Cylinder Plumbing Plumbing Connection...

Page 4: ...not suitable for installation above 400 metres altitude and has NO WARRANTY for freeze damage if installed above 400 metres altitude This solar water heater is designed to be installed with an Aquamax...

Page 5: ...f persons living in the house require additional safety protection from potential scalding This will keep the hot water supply temperature to the bathroom s and ensuite s below 50 C which will reduce...

Page 6: ...r outlet to the solar control unit Note The Aquamax warranty does not cover damage caused by freeze conditions when the electrical circuit or electrical supply to the solar control unit is turned off...

Page 7: ...lar collectors to the solar storage cylinder can become very hot Warning If the power supply cord or plug to the solar control unit or gas booster is damaged it must be replaced by a qualified person...

Page 8: ...heat the water by solar gain The time to reheat the water in the solar storage cylinder will depend upon time of year time of day and prevailing weather conditions however the gas booster will provide...

Page 9: ...5 years of installation Cleaning the Solar Collector Glass Ensure the solar collector glass is free of dust salt spray or any other matter which may reduce the effectiveness of the solar collectors If...

Page 10: ...r can have a detrimental effect on the operation and or life expectation of the solar storage cylinder and pressure temperature relief valve Where there is a changeover from one water supply to anothe...

Page 11: ...de and replacement if necessary refer to Periodic Maintenance on page 6 and Anode on page 8 Water Chemistry Levels Affecting Warranty The Aquamax warranty of this solar water heater will not cover res...

Page 12: ...LED is flashing switch off the electrical supply at the power outlet to the solar control unit for five 5 seconds and then switch back on again If the green LED remains off or the red LED recommences...

Page 13: ...ll occur when the solar heated water temperature is lower than the preset outlet temperature setting of the gas booster This may be experienced during periods of low solar energy gain or if there has...

Page 14: ...mode power on for less than 48 hours Green rapid pulse Circulating water through collectors 3 x green Circulating water through collectors system power on for less than 48 hours no green remains off P...

Page 15: ...d to Installers must be competently trained in Height Hazard Assessment Working at Height Procedures Assessment Use Wearing of correct height safety equipment harnesses etc All other relevant safety f...

Page 16: ...pplied with solar water heater Tank Water Supply If the solar water heater is supplied with water from a tank supply and a pressure pump system is not installed then the bottom of the supply tank must...

Page 17: ...ot necessary to allow for free air circulation under the base of the solar storage cylinder For outdoor installation the solar storage cylinder shall be installed freestanding on a level and stable co...

Page 18: ...de The dimensions shown in the table below are the minimum clearance distances from the flue terminal These clearances must be observed at all times Below eaves balconies and other projections 300 Fro...

Page 19: ...d Purging the Solar Collectors on page 9 The solar control unit is mounted on the side of the solar storage cylinder and controls system operation The solar control unit has a power cord which connect...

Page 20: ...frame as defined in the Building Code of Australia Australian New Zealand Standard AS NZS 1170 2 2002 and the Australian Standard AS 4055 2006 and provides an acceptable method of installation where i...

Page 21: ...ive compression fittings must use brass or copper olives Use thread sealing tape or approved thread sealant on all other fittings never use hemp A disconnection union must always be provided at the co...

Page 22: ...the solar water heater is operated Before fitting the PTR valve make sure the valve probe has not been bent Seal the valve thread with thread sealing tape never use hemp and ensure the tape does protr...

Page 23: ...ongly recommended the pipe work downstream of the relief valve be capable of carrying water exceeding 99 C Failure to observe this precaution may result in damage to pipe work and property Note A drai...

Page 24: ...nstructions supplied with the solar controller kit for details on the installation and plumbing of the solar controller kit Refer to Solar Controller Kit Installation on page 18 for an overview of the...

Page 25: ...ipe length solar cold solar hot and number of 90 bends Pipe Size 1 or 2 Collectors 3 Collectors Pipe Length 90 Bends Pipe Length 90 Bends DN15 40 metres 20 30 metres 20 DN20 NR NR 40 metres 20 For eac...

Page 26: ...copper pipe avoiding accidental contact with the solar pipe work which can become very hot as high temperature water can flow from the solar collectors to the solar storage cylinder reducing pipe heat...

Page 27: ...must always be installed after the non return valve and be the last valve prior to the solar storage cylinder Warning A non return valve MUST BE installed on the cold water line to the solar storage c...

Page 28: ...perature Zone Plumbing Diagrams Two Temperature Zone Plumbing Diagram Gas Boosted Solar System with Integrated Gas Booster Two Temperature Zone Plumbing Diagram Gas Boosted Solar System with Remote Ga...

Page 29: ...installed as part of a circulated hot water flow and return system in a building provided the following requirements are met The gas boosters preset outlet temperature setting is set to a minimum of...

Page 30: ...29 Circulated Flow Return Plumbing Diagram Gas Boosted Solar System with Remote Gas Booster...

Page 31: ...lector circuit with water under mains pressure and checking the pipe work for leaks during the commissioning procedure can be substituted for the pressure testing of the collector circuit If pressure...

Page 32: ...ing should be noted It is necessary to check the gas supply pressure at the inlet to the gas booster and also the minimum gas test point pressure and the maximum gas test point pressure of the gas boo...

Page 33: ...close the bleed valve To refill the solar collectors after draining and reinstate the solar water heater 1 Open all hot water taps in premises including shower s 2 Fully open cold water isolation val...

Page 34: ...torage cylinder and tighten 2 Open all hot water taps in premises including shower s 3 Fully open cold water isolation valve on cold water line to solar storage cylinder This will purge air from hot w...

Page 35: ...60 165 Weight kg Empty 100 90 75 60 Full 515 415 335 225 Dimensions A mm 1525 1535 1215 1410 B mm 230 215 215 190 C mm 565 590 530 530 D mm 685 620 620 487 H mm 1760 1755 1435 1605 Max Supply Pressure...

Page 36: ...5 Dimensions A mm 1525 1535 1215 1410 B mm 230 215 215 190 C mm 565 590 530 530 D mm 685 620 620 487 E mm 20L Booster N A 1170 850 1020 26L Booster 1135 1130 810 980 H mm 1760 1755 1435 1605 Max Suppl...

Page 37: ...36 This page is intentionally blank...

Page 38: ...en the nearest branch office or Aquamax Accredited Service Agent s office and the installed site shall be the owner s responsibility 2 5 Where the water heater is installed in a position that does not...

Page 39: ...r heater the duration of the protection afforded by this warranty may be greater than what is set out above Please call 1800 676 000 for details 4 Entitlement To Make A Claim Under This Warranty 4 1 T...

Page 40: ...tomer in the event that a claim is made under the Aquamax warranty Plumber Name Company Plumber s licence number Compliance Certificate if applicable in your state Installation date Model serial numbe...

Reviews: