1. Turn ON the OC FOLD parameter:
From the Set screen, press the MORE soft key. In the next window press the SYSTEM soft key.
In the System Parameters Menu, use the
(
,
)
arrow keys to highlight the “OC FOLD”
parameter. Press EDIT to change the parameter.
Press CHANGE to set the highlighted parameter to ON. Press ENTER to save changes. Press EXIT
twice to return to the Set screen.
2. Program a current Hi-Limit, which represents the constant current you will provide to
the load:
Press EDIT from the Set screen.
Use the
(
,
)
arrow soft keys to highlight the “A Hi-Lmt” parameter. Press EDIT to change the
parameter.
Use the Numeric Keypad to enter the desired current limit. Press ENTER to save changes and
then press EXIT to return to the Edit Parameters Menu. The limit set will be the constant current
output.
3. Program the voltage:
From the Edit Parameters Menu, use the
(
,
) arrow soft keys to highlight the “Voltage”
parameter. Press EDIT to change the parameter.
Using the Numeric Keypad enter the voltage which should be set higher than the nominal load
voltage. This allows the current to adjust to the Hi-Limit value.
Press ENTER after you enter the voltage and press EXIT twice to return to the Set screen.
Note: For advanced features and functions such as linking and 3Ø setup
please refer to the product manual.
CONSTANT CURRENT MODE