8.1 YC600B Microinverter Datasheet
Note 1: Utility Interconnection Voltage and Frequency Trip Limits and Trip Times
Voltage and frequency limits for utility Interaction
Condition
Simulated utility source
Maximum time (sec)
(cycles) at 60 Hza
before cessation of
current to the
simulated utility
Trip time accuracy
Voltage (V)
Frequency
(Hz)
A
< 0.50 Vnor
Rated
80ms
+/-80ms
B
0.50 Vnor
≤
V < 0.88 Vnor
Rated
1000ms
+/-200ms
C
1.10 Vnor < V < 1.20 Vnor
Rated
1000ms
+/-200ms
D
1.20 Vnor
≤
V
Rated
80ms
+/-80ms
E
Rated
f > 60.5
160ms
+/-200ms
F
Rated
f < 59.3
160ms
+/-200ms
2022/06/29 REV1.5
(1)
Nominal voltage/frequency range can be extended beyond nominal if required by the utility.
(2)
Limits may vary. Refer to local requirements to define the number of microinverters per branch in your area.
(3)
The inverter may enter to power de-grade mode under poor ventilation and heat dissipation installation environment.
(4)
Recommend no more than 80 inverters register to one ECU for stable communication.
(5)
To be eligible for the warranty, APsystems microinverters need to be monitored via the EMA portal. Please refer to our warranty
T&Cs available on latam.APsystems.com.