SHEET 6 – USING THE VENTILATION FEATURE OF THE DEHUMIDIFIER

PARTS NEEDED 

(ADDITIONAL 

PARTS MAY BE REQUIRED)

•  Model 6506 damper
•  Model 8052 Outdoor 

Temperature Sensor (optional)

•  Model 4010 10VA transformer
•  6" insulated duct, fittings and 

hardware

•  Intake hood
•  Thermostat wire

FIGURE 1 

– VENTILATION DUCT LOCATION

FIGURE 2 

– DEHUMIDIFY VENTILATION AIR

SET UP THE DEHUMIDIFIER FOR VENTILATION

1. 

With 

OFF

 showing on the control, press the MODE 

button for 3 seconds to enter the Installer Set Up menu.

2. 

Press the MODE button until 

VENT DISABLED

 appears.

3. 

Press the 

 or 

 button to change to 

VENT 

ENABLED

.

4. 

Press the MODE button and 

V   

 !" #

 will be 

displayed. Press the 

 or 

 button to toggle 

between:

TIMED:

 no temperature limits.

AUTO – B:

 Ventilation not allowed if ODT > 100°F 

or ODT < 0°F; allowed only when heating if 
0°F < ODT < 20°F.

AUTO – C:

 Ventilation not allowed if ODT > 100°F or 

ODT < 0°F.

AUTO – D:

 Ventilation not allowed if ODT > 90°F; 

allowed only when heating if 0°F < ODT < 40°F.

5. 

Press the MODE button, the use the 

 or 

 button 

to set the Vent Time (minutes/hour).

6. 

Press the MODE button repeatedly until 

DONE

 appears 

on the display.

VENTILATION WIRING

N.C. DAMPER

120

VAC 

24

VAC 

G

HVAC

EQUIPMENT

THERMOSTAT

OR ZONE

CONTROL

BOARD

R

C

G

W

Y

ODT

SENSOR

DH  DH

REMOTE

+
-

A
B

HVAC EQUIP

GhRf

CfGs

W

Y

DAMPERS

VENT

DEH

FLOAT

SWITCH

DEHUMIDIFIER

CONTROL

BOARD 

NC
NO

ODT SENSOR

R

C

W

Y

EXISTING WIRE

NEW WIRE

USING THE DEHUMIDIFIER TO PRE-CONDITION THE VENTILATION AIR

The dehumidifier can be used to remove moisture from the ventilation air 

before

 

it is delivered to the home. Install the ventilation duct to the dehumidifier inlet 
duct as shown in 

FIGURE 2

. The control on the dehumidifier must be used for the 

Primary Zone (i.e. an external control cannot be used) in this installation. If the RH 
of the incoming air is above the setting on the control the air will be dehumidified.

Install a ventilation duct with a normally closed Model 6506 damper to the return duct of the HVAC system (see 

FIGURE 1

) and wire the dehumidifier 

to the HVAC system as shown in 

V

   !

$

ATION WIRING

. The outdoor temperature (ODT) sensor is used to limit ventilation if the outdoor temperature 

gets too hot or too cold (see 

SET UP THE DEHUMIDIFIER F

O%

V

  !

$

ATION

 below). If temperature limits are not needed, the ODT sensor does 

not have to be installed. Follow the set up instructions below and set the number of minutes per hour that ventilation will be needed (refer to the 
Installation Manual for details on determining how much ventilation is needed). Whenever the heating or cooling turns on, or when the dehumidifier 
turns on, the dehumidifier will open the damper and bring in fresh outdoor air. If the equipment doesn’t run for the set number of minutes, the 
dehumidifier will turn on HVAC fan at the end of the hour to ensure ventilation needs are met.

7

Summary of Contents for E080

Page 1: ...76 in the living space 3 Two Zone Not recommended in HVAC zoning applications Whole house Basement Internal 4 External in Primary 5 Two Zone Not recommended in HVAC zoning applications Basement Whole...

Page 2: ...RATION The dehumidifier will automatically sample the air by turning on its blower and the HVAC blower if this option has been wired see WIRING INTERNAL CONTROL above and measuring the relative humidi...

Page 3: ...or Model 8910 Home Comfort Control must have a normally open NO all Aprilaire controls are normally open type or normally closed NC dry contact output and must be installed in the space that is going...

Page 4: ...can be installed in any convenient location within the living space while the dehumidifier is installed in the space that is going to be dehumidified such as a crawl space attic or basement The relati...

Page 5: ...ary Zone If there is no need for dehumidification in the Primary Zone the dehumidifier will then sample the air in the Secondary Zone When sampling in the Primary Zone the dehumidifier will energize t...

Page 6: ...ampers are not energized while the dehumidifier blower runs and the RH is measured If the RH is above the setting on the control the compressor will turn on and the Secondary Zone will be dehumidified...

Page 7: ...P Gh Rf Cf Gs W Y DAMPERS VENT DEH FLOAT SWITCH DEHUMIDIFIER CONTROL BOARD NC NO ODT SENSOR R C W Y EXISTING WIRE NEW WIRE USING THE DEHUMIDIFIER TO PRE CONDITION THE VENTILATION AIR The dehumidifier...

Page 8: ...AprilairePartners com P O Box 1467 Madison WI 53701 1467 800 334 6011 F 608 257 4357 Printed in USA 2020 Aprilaire Division of Research Products Corporation 10015107 B2209060A 11 20...

Reviews: