Aprilaire Automatic Humidifier Control Safety And Installation Instructions Manual Download Page 2

3

2

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3
System Checkout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 21
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 22

TABLE OF CONTENTS

WARNING

1. 120 volts may cause serious injury from electrical

shock. Disconnect electrical power to the HVAC
system before starting installation.

2. Sharp edges may cause serious injury from cuts.

Use care when cutting plenum openings and
handling ductwork.

CAUTION

1. Do not set humidity higher than recommended.

Condensation damage may result.

2. Do not set humidity up to recommended levels if

there is condensation on the inside of windows of
any unheated living space. Condensation damage
may result.

3. Do not mount the Humidifier Control on the supply

plenum or duct. The unit cannot withstand supply
temperatures and will malfunction.

4. When installing the Humidifier Control on a

counterflow furnace, ensure the blower continues
to run after a heat call is satisfied to eliminate high
temperatures from damaging the Humidifier Control.

5. Do not mount the Humidifier Control downstream of

the bypass outlet. False humidity conditions will
cause the humidifier to operate incorrectly.

6. Avoid installing the Humidifier Control with the display

facing downward to prevent the Humidifier Control
from incorrectly measuring the relative humidity
(RH) in the duct.

THESE INSTALLATION INSTRUCTIONS ARE FOR THE

APRILAIRE DIGITAL HUMIDIFIER CONTROL ONLY!

For Aprilaire

®

humidifier installation, follow Aprilaire

Humidifier Installation Instructions.

INSTALLATION

STEP 1: Unpack the Humidifier Control Carton

Make sure all components are present (see

Figure A

):

A

. Humidifier Control

B.

Outdoor Temperature Sensor

C.

Manual Mode Label

D.

Manual Mode Resistor Case

B

A

C

D

Figure A

90-1201

Summary of Contents for Automatic Humidifier Control

Page 1: ...ns WARNING ATTENTION INSTALLER This product must be installed by a qualified heating and air conditioning contractor Failure to do so could result in serious injury from electrical shock READ COMPLETE...

Page 2: ...en installing the Humidifier Control on a counterflow furnace ensure the blower continues to run after a heat call is satisfied to eliminate high temperatures from damaging the Humidifier Control 5 Do...

Page 3: ...when the indicator light turns on reminding you to change your water panel If your Control came with a humidifier the Control is pre set for the humidifier If the installation site has a 3 month or s...

Page 4: ...midifier Control sensor gasket is seated tightly around the drilled hole Do Not Install Control Without Gasket Reattach cover and knob DUCT FIBER BOARD MOUNT After location for Control is selected cut...

Page 5: ...UCT SHEET METAL PLATE GASKET SCREW x2 INSIDE OF RETURN DUCT Figure E Digital Humidifier Control 24V Terminals 90 1397 H W G Cf ODT B A C R OUTDOOR TEMPERATURE SENSOR OR MANUAL MODE RESISTOR CONTINUOUS...

Page 6: ...utdoor Temperature Sensor The location of the Outdoor Temperature Sensor must meet these three requirements 1 Must be mounted on North East or West side of house out of direct sunlight 2 Must be at le...

Page 7: ...de label to the cover aligning the sticker and knob holes H W G Cf ODT B A C R Figure J 90 1220 STEP 9 Route the Wire from Control to Sensor Run wire to the outdoor temperature sensor Sensor is not af...

Page 8: ...into a constant power source other than the heating ventilating air conditioning equipment HVAC blower circuit The transformer can be powered off the 120 VAC line at the junction box before it enters...

Page 9: ...ES BROWN WIRES 400 SERIES YELLOW WIRE WHITE WIRE NOTE PLUMB HUMIDIFIER TO HOT WATER WHEN USING THIS WIRING CONFIGURATION 90 1398 USING HUMIDIFIER CONTROL TO ACTIVATE HVAC BLOWER ON CALL FOR HUMIDITY F...

Page 10: ...ed NOTE The Water Panel Change Indicator must be set to the OFF position for this option Figure P 90 1222 24 VAC TRANSFORMER OUTDOOR TEMPERATURE SENSOR OR MANUAL MODE RESISTOR HEAT PUMP TERMINAL STRIP...

Page 11: ...ctivate with the Humidifier Control in the Test Reset position refer to the troubleshooting guide 7 Setting the Humidifier Control If the home is occupied set the Humidifier Control to Normal For Manu...

Page 12: ...ted to the ODT terminals on the Humidifier Control 2 Measure the resistance of the Outdoor Temperature Sensor by removing the leads from the Humidifier Control terminals and measuring the resistance a...

Page 13: ...ons Check Blower Activation Relay Model 4851 if used for correct installation see Model 4851 instructions Make sure that the saddle valve is open In Test Reset mode the humidifier will operate for 1 m...

Page 14: ...matic Mode Only Make sure that the Outdoor Temperature Sensor is located at least 3 feet away from all exhaust vents Automatic Mode Only If Outdoor Temperature Sensor is mounted in the fresh air intak...

Page 15: ...UBLESHOOTING PROCEDURE Check for steady 22 VAC to 30 VAC across the R and C terminals of the Humidifier Control with a voltmeter Check with a voltmeter that the HVAC signal across the W G and Cf termi...