Aprilaire Automatic Humidifier Control Safety And Installation Instructions Manual Download Page 14

27

26

SYMPTOM

Humidifier operates only in “Test/Reset” mode

• If outdoor temperature is greater than 60°F or less than

-30°F, the Humidifier Control will only operate in the
“Test/Reset” mode (for 1 minute).

• If the humidity level in the home is higher than the

Humidifier Control knob setting, the Humidifier Control will
not operate the humidifier.

TROUBLESHOOTING PROCEDURE

• Measure the resistance of the Outdoor Temperature Sensor

by removing the leads from the Humidifier Control terminals
and measuring the resistance across the wires with an
ohmmeter. Confirm the reading with the temperature in

Table 1

. (For Manual Operation, verify that the resistance

across the leads of the Manual Mode Resistor Case is
between 44K and 48K ohms). Reconnect the ODT leads.
If the resistance value does not match the temperature
value, replace the Outdoor Temperature Sensor.

• Make sure that the Outdoor Temperature Sensor is mounted

completely outside the house on the North, East or West
side of the house and out of direct sunlight. (Automatic
Mode Only)

• Make sure that the Outdoor Temperature Sensor is located

at least 3 feet away from all exhaust vents. (Automatic
Mode Only)

• If Outdoor Temperature Sensor is mounted in the fresh

air intake duct, make sure that the sensor is no more than
3 feet from the outside wall. (Automatic Mode Only)

SYMPTOM

Humidifier operates constantly

• If the humidity level in the home is less than the Humidifier

Control knob setting and there is a continuous fan call or
heat call (depending on setup), the Humidifier Control will
operate the humidifier until the humidity level is higher than
the Humidifier Control knob setting.

TROUBLESHOOTING PROCEDURE

• In the “Test/Reset” mode, verify that the humidifier turns

off after 1 minute.

• Check the Outdoor Temperature Sensor resistance and

location, as instructed on the previous page.

• Rotate the Humidifier Control knob counterclockwise to the

“Off” position, and observe whether the humidifier turns
off. If the humidifier still operates in the “Off” position,
perform the following:

1. Check the wiring diagram for correct Humidifier Control

Installation.

2. Remove the wires from the “H” terminals on the

Humidifier Control. If the humidifier continues to operate,
replace the solenoid valve.

Summary of Contents for Automatic Humidifier Control

Page 1: ...ns WARNING ATTENTION INSTALLER This product must be installed by a qualified heating and air conditioning contractor Failure to do so could result in serious injury from electrical shock READ COMPLETE...

Page 2: ...en installing the Humidifier Control on a counterflow furnace ensure the blower continues to run after a heat call is satisfied to eliminate high temperatures from damaging the Humidifier Control 5 Do...

Page 3: ...when the indicator light turns on reminding you to change your water panel If your Control came with a humidifier the Control is pre set for the humidifier If the installation site has a 3 month or s...

Page 4: ...midifier Control sensor gasket is seated tightly around the drilled hole Do Not Install Control Without Gasket Reattach cover and knob DUCT FIBER BOARD MOUNT After location for Control is selected cut...

Page 5: ...UCT SHEET METAL PLATE GASKET SCREW x2 INSIDE OF RETURN DUCT Figure E Digital Humidifier Control 24V Terminals 90 1397 H W G Cf ODT B A C R OUTDOOR TEMPERATURE SENSOR OR MANUAL MODE RESISTOR CONTINUOUS...

Page 6: ...utdoor Temperature Sensor The location of the Outdoor Temperature Sensor must meet these three requirements 1 Must be mounted on North East or West side of house out of direct sunlight 2 Must be at le...

Page 7: ...de label to the cover aligning the sticker and knob holes H W G Cf ODT B A C R Figure J 90 1220 STEP 9 Route the Wire from Control to Sensor Run wire to the outdoor temperature sensor Sensor is not af...

Page 8: ...into a constant power source other than the heating ventilating air conditioning equipment HVAC blower circuit The transformer can be powered off the 120 VAC line at the junction box before it enters...

Page 9: ...ES BROWN WIRES 400 SERIES YELLOW WIRE WHITE WIRE NOTE PLUMB HUMIDIFIER TO HOT WATER WHEN USING THIS WIRING CONFIGURATION 90 1398 USING HUMIDIFIER CONTROL TO ACTIVATE HVAC BLOWER ON CALL FOR HUMIDITY F...

Page 10: ...ed NOTE The Water Panel Change Indicator must be set to the OFF position for this option Figure P 90 1222 24 VAC TRANSFORMER OUTDOOR TEMPERATURE SENSOR OR MANUAL MODE RESISTOR HEAT PUMP TERMINAL STRIP...

Page 11: ...ctivate with the Humidifier Control in the Test Reset position refer to the troubleshooting guide 7 Setting the Humidifier Control If the home is occupied set the Humidifier Control to Normal For Manu...

Page 12: ...ted to the ODT terminals on the Humidifier Control 2 Measure the resistance of the Outdoor Temperature Sensor by removing the leads from the Humidifier Control terminals and measuring the resistance a...

Page 13: ...ons Check Blower Activation Relay Model 4851 if used for correct installation see Model 4851 instructions Make sure that the saddle valve is open In Test Reset mode the humidifier will operate for 1 m...

Page 14: ...matic Mode Only Make sure that the Outdoor Temperature Sensor is located at least 3 feet away from all exhaust vents Automatic Mode Only If Outdoor Temperature Sensor is mounted in the fresh air intak...

Page 15: ...UBLESHOOTING PROCEDURE Check for steady 22 VAC to 30 VAC across the R and C terminals of the Humidifier Control with a voltmeter Check with a voltmeter that the HVAC signal across the W G and Cf termi...