4
5
WIRING
(CONTINUED)
8052
OUTDOOR
SenSOR
8051
FLUSH MOUnT
SenSOR
24 vAC
COMMOn
8082
8081
8800
The Support Module has 6 dip switches, as shown in the
diagram to the right, that must be configured. The 8800
thermostat must be powered down for 90 seconds for dip
switch settings to take effect.
1
2
3
4
5
6
OFF
ON
OFF
ON
ADDRESS
ADDRESS
ADDRESS
ADDRESS
MONITOR (S1)
CONTROL (S1)
MONITOR (S2)
CONTROL (S2)
SPARE
SPARE
T1/T2 (S1)
ONBOARD SENSOR
DIp SWITCH CONFIGURATION
each Support Module must have its own unique address.
The address is set as shown in the diagram to the right.
SUppORT MODUlE ADDRESS SElECTION – DIp SWITCH 1 & 2
ADDRESS 1
ADDRESS 2
ADDRESS 3
ADDRESS 4
OFF
ON
OFF
ON
OFF
ON
OFF
ON
This dip switch determines if sensor 1 is a controlling (on) or monitoring (off) temperature.
If the switch is set to off, sensor 1 will monitor the temperature. All monitoring values will cycle through the
message center on the thermostat.
If the support module is set to address 1, sensor 1 is set to monitor, and
the 8800 thermostat does not have an outdoor temperature sensor attached then the 8800 thermostat will
use sensor 1 as the outside temperature value.
If the switch is set to on, the 8800 thermostat will use sensor 1 to control and will display the temperature as the
controlling temperature on the 8800 thermostat. If multiple sensors are set to control, the values will be averaged
and the average value will be used to control the 8800 thermostat. The average value will be displayed as the
controlling temperature on the 8800 thermostat.
SENSOR 1 MODE – DIp SWITCH 3
WIRING DIAGRAM
90-1649
This dip switch determines if sensor 1 uses the value from the on board temperature sensor (on) or from a remote
temperature sensor (off) attached to T1&T2. If the dip switch is set to on, the Support Module will use the on board
temperature sensor. If the switch is set to off, the Support Module will use the remote temperature sensor wired to
T1&T2.
Note: If the switch is set to off and there is no temperature sensor wired to T1&T2 then no value will
be reported for sensor 1 or sensor 2 and “CHECK SM” message will be displayed at the 8800 thermostat.
SENSOR 1 SElECTION – DIp SWITCH 6