The dehumidifier is supplied with two 8” round collars. An integral backflow damper is installed in the outlet collar. In a ducted installation, the 

dehumidifier pulls air from the living space or HVAC return duct and supplies the dehumidified air to the HVAC supply duct (See 

Figures 5, 6 & 7

). 

DUCTED INSTALLATION

•  Move supply collar to the desired location, if necessary. (See 

Supply Collar

 in 

SET-UP

 Section)

•  The unit can be ducted to the supply or both the return and supply. The dehumidifier inlet ducting must be a minimum of 6” upstream of the 

HVAC system air cleaner and the outlet must be ducted a minimum of 6” downstream of the cooling coil.

•  Use the least amount of ductwork possible. To ensure best performance, do not exceed a total of 50 feet of duct installed in accordance with 

SMACNA Standards. UL approved, 8” diameter, insulated duct is recommended for all connections.

•  All joints and seams must be sealed.

DUCTING 

HVAC / FURNACE

115 VAC

DEDICATED

CIRCUIT

DEHUMIDIFIER

SUPPLY DUCT

RETURN

DUCT

A-COIL

DEHUMIDIFIED AIR IS SUPPLIED

DOWNSTREAM

  FROM A-COIL TO

MINIMIZE EVAPORATION OFF A-COIL

AIR IS PULLED

FROM MAIN

RETURN DUCT

DEHUMIDISTAT WITH 

SET POINT KNOB

CONDENSATE HOSE

(TO COMMON DRAIN OR OUTSIDE)

FIGURE 5 – Basement Installation

90-1423

MAIN RETURN 

DUCT

DEHUMIDIFIER

MAIN SUPPLY DUCT

CONDENSATE

HOSE

(TO COMMON

DRAIN OR

OUTSIDE)

PRINCIPAL

LIVING SPACE

115 VAC

DEDICATED

CIRCUIT

AIR FILTER

ACCESS

DOOR

HVAC/FURNACE SYSTEM 

SHOWN IN HORIZONTAL

ORIENTATION

DEHUMIDIFIED AIR IS SUPPLIED

DOWNSTREAM 

FROM EVAPORATOR COIL

TO MINIMIZE EVAPORATION OFF COIL

HVAC EVAPORATOR COIL

RELOCATE DEHUMIDISTAT

TO LIVING SPACE

FIGURE 7 – Attic Installation

90-1423

DEHUMIDIFIED AIR IS SUPPLIED 

DOWNSTREAM 

FROM A-COIL TO 

MINIMIZE EVAPORATION OFF A-COIL

115 VAC

DEDICATED

CIRCUIT

A-COIL

SUPPLY DUCT

HVAC / FURNACE

CONDENSATE HOSE

ON DEHUMIDIFIER

(TO COMMON DRAIN

OR OUTSIDE)

DEHUMIDIFIER

FIGURE 6 – Equipment Room/Closet Installation

90-1423

Note 1:

 Attic installations require the following.

1.  The dehumidistat must be removed from the 

unit and relocated in the living space. An 

insulated cover plate is provided to cover the 

dehumidistat opening.

2.  The dehumidifier must be installed in a 

secondary drain pan with a float switch. 

Note 2:

 Vibration isolators placed under the 

dehumidifier feet are recommended when the 

dehumidifier is installed on ceiling joists.

3

Summary of Contents for 1730A

Page 1: ...e required to protect from moving parts and electrical components CAUTION 1 Do not use in pool applications 2 If unit has been shipped or stored on its side wait 24 hours before running 3 Do not use s...

Page 2: ...y 5 feet above the floor on an inside wall of the living space Do not locate dehumidistat in the direct path of drafts from open doors and windows Do not install where operation might be affected by l...

Page 3: ...ORATION OFF A COIL AIR IS PULLED FROM MAIN RETURN DUCT DEHUMIDISTAT WITH SET POINT KNOB CONDENSATE HOSE TO COMMON DRAIN OR OUTSIDE Figure 5 Basement Installation 90 1423 MAIN RETURN DUCT DEHUMIDIFIER...

Page 4: ...e wired to activate the HVAC blower during dehumidification This is recommended because it offers better circulation and balancing of the indoor air conditions Note Running the HVAC blower during dehu...

Page 5: ...E terminals from the circuit board remove the two wires and cut off bare leads Once cut the wires may remain in the unit 9 Run a 2 wire cable 18 22AWG from the dehumidifier to the wall mount location...

Page 6: ...ow the wiring access panel Verify the green LED is on The green LED is on when power is applied to the system 4 Rotate the dehumidistat knob fully clockwise to ON position 5 If setup is correct the de...

Page 7: ...ocedure Red LED On Blower compressor not running Open Float Switch If float switch not installed confirm jumper installed at FLOAT SWITCH terminals If float switch installed confirm switch is not open...