UIM
ip
- TAD
02.03.2017
5 / 19
4
O
PERATIONAL
D
ESCRIPTION
The
UIM
ip
features two different modes, the “Normal Mode” and the “Boot Mode”.
In this chapter it is explained how to
assign the individual physical address
4.1
N
ORMAL
M
ODE
According either to the factory default settings or the latest parameter settings downloaded
from the ETS (also other tools) in normal operating mode the
UIM
ip
operates
as it is supposed to and LEDs 1, 2 light green.
Green
Red
LED 1
Bus State LAN
On: LAN line OK
Off: LAN line error
N.A.
LED 2
Bus State KNX
On: KNX line OK
Off: KNX line error
N.A.
LED 3
Traffic LAN
Off
Blinking:
transmission error LAN line
LED 4
Traffic KNX
Blinking:
bus traffic KNX TP line
Blinking:
transmission
error
KNX
TP
line
LED 5
Programming
N.A.
On: device in Boot Mode
Blinking: LAN line error
4.1.1
P
ROGRAMMING
B
UTTON AND
P
HYSICAL
A
DDRESS
A
SSIGNMENT
To
download
the
desired
physical
address
or
a full ETS setting into the device, during the procedure
the programming button ( ) needs to be pressed.
(The programming button is used to put the device into
“Program Mode”). With the ETS the physical address can
be assigned to the device by setting the desired address in
the properties window of the ETS, starting the download
and pressing the programming button. After assignment
the device restarts itself. (A blinking red LED 5 indicates
that the Ethernet cable is not properly connected.)
To commission the device a PC with ETS and an interface
connection (IP, USB) to the databus is required. The
device is supplied with the individual physical address
15.15.255. The KNX product database entry (available for
ETS3 and higher) can be downloaded from our website or
the KNX Online Catalog App.
Picture 3: Properties window
C