Apricum UIMip Documentation Download Page 1

Details, modifications and corrections may be subject to change without notice.

 

Apricum gives no warranty for the accuracy of the document. 

The reproduction, transmission and use of this document or its contents is not permitted without written authority. All rights reserved.

 

 

D

OCUMENTATION

 

UIM

ip

 

 

 

 
 

T

ECHNICAL AND 

A

PPLICATION

 

D

ESCRIPTION

 

 
 
 

Authors: Manouchehr Ghahramanian Golzar, Peter Hauner 

 

Last Modification: 2017-03-02

 

 
© 2001-2017 Apricum d.o.o. 
Mažuranićeva 4, 21312 Podstrana, Hrvatska 

Summary of Contents for UIMip

Page 1: ... The reproduction transmission and use of this document or its contents is not permitted without written authority All rights reserved DOCUMENTATION UIMip TECHNICAL AND APPLICATION DESCRIPTION Authors Manouchehr Ghahramanian Golzar Peter Hauner Last Modification 2017 03 02 2001 2017 Apricum d o o Mažuranićeva 4 21312 Podstrana Hrvatska ...

Page 2: ...ware Update 6 4 3 KNX Telegrams in the IP Network 7 5 Application Description 7 6 ETS Parameters 8 6 1 General 8 6 2 IP Configuration 8 7 Web Front End 10 7 1 Accessing the Device 10 7 1 1 Via the Windows Network with UPnP 10 7 1 2 Via the MAC Address 10 7 1 3 Via the IP Address 10 7 2 Device Info 11 7 3 KNX 11 7 4 Update 12 7 5 Tunneling Addresses Additional Physical Addresses 14 8 State of Deliv...

Page 3: ... BUSY on the bus etc Picture 1 Front view 1 Bus state LAN LED 2 Bus state KNX TP line LED 3 Bus traffic LAN line LED 4 Bus traffic KNX TP line LED 5 Programming LED A Ethernet connector B Function button C Program button D KNX connector 1 Information basics about tunnelling and device management The presence of the Internet Protocol IP has led to the definition of KNXnet IP KNXnet IP provides the ...

Page 4: ...is using LAN as a fast medium to exchange telegrams between the lines and or areas The UIMip is featuring a high internal amount of communication buffers being capable of smoothening peaks in the communication load course Using a high internal amount of communication buffers is suitable for networks with a high bus load UPnP is available to discover the device in an IP network In terms of topology...

Page 5: ...ne LED 5 Programming N A On device in Boot Mode Blinking LAN line error 4 1 1PROGRAMMING BUTTON AND PHYSICAL ADDRESS ASSIGNMENT To download the desired physical address or a full ETS setting into the device during the procedure the programming button needs to be pressed The programming button is used to put the device into Program Mode With the ETS the physical address can be assigned to the devic...

Page 6: ...button 3 s When operating in Boot Mode it is possible to update the UIMip s firmware For more detailed information concerning the update procedure please refer to the section Update In order to switch from Normal Mode to Boot Mode it is necessary to begin the firmware update procedure and use the Request Update button in the Web Front End 1 Press the programming button in Normal Mode 2 Press the f...

Page 7: ...ub line addresses For more information about the additional tunneling addresses please refer to Tunneling Addresses Additional Physical Addresses 5 APPLICATION DESCRIPTION The IP Interface is designed for use in 10 100 BaseT networks compliant to IEEE802 3 The device features an AutoSensing function and sets the baud rate 10 Mbit or 100 Mbit automatically The IP address of the device can be receiv...

Page 8: ...ce name 30 signs max providing an easy search of the device with the ETS or any KNXnet IP visualisation system Note If the Host name is changed by an ETS4 download a manual restart is recommended 6 2 IP CONFIGURATION Picture 5 IP configuration ETS Text Selection Factory default Comment DHCP use do not use use If DHCP is used no parameterisation of the IP parameters must be done If DHCP is not used...

Page 9: ... address 0 255 0 255 0 255 0 255 0 0 0 0 IP Byte 1 to 4 manual input Net mask 0 255 0 255 0 255 0 255 255 255 255 0 NM Byte 1 to 4 manual input Gateway 0 255 0 255 0 255 0 255 0 0 0 0 GW Byte 1 to 4 manual input Note The configuration of the IP connectivity Host name IP address KNX multicast address is not updated automatically after an ETS download To get these values updated it is essential exec...

Page 10: ...ual restart is recommended Then wait until the device gets visible in the list of network devices If it is still not visible make sure that the UPnP function of the network is enabled 7 1 2VIA THE MAC ADDRESS The MAC address is printed on a label of the UIMip housing Use this MAC address of the UIMip without brackets as described here http knx ipif XX YY ZZ 8080 Example XX byte 4 of the MAC addres...

Page 11: ...Program Mode of the UIMip can be turned On or Off This function is similar to the programming button function With this the regarded device is easy to distinguish from other interfaces in the same IP network It can also be noticed what the particular device is currently processing after a change in the settings for example With the Set button and the ETS it is possible to set the Tunneling Address...

Page 12: ... and continue with step 3 refresh request update Step 1 Open the Update tab of the Web front end Picture 10 Update Step 2 Either use the Change Program Mode function in the KNX tab or press the programming button once Picture 11 Program mode Step 3 After the Program Mode is turned to On give a short key press to the function button Then the refresh button in the Update tab needs to be pressed Alte...

Page 13: ...select the update file and enter Boot Mode Picture 13 Request update Step 5 The device now switches to Boot Mode The update file can be selected and uploaded Pressing the Abort button cancels the firmware update procedure and the device exits the Boot Mode Picture 14 Select update file ...

Page 14: ...ETS and select the UIMip as the Current Interface In the IP Tunneling window the already assigned host physical address can be read Picture 15 First additional physical address tunnelling address Step 2 Type the additional physical address into the Individual Address field Click on the Test button If the green Ok appears the first tunneling address is already set In this example it is set to 9 1 2...

Page 15: ...All dimensions shown here are specified in mm The device width is 2 modules at 18 mm Picture 17 Dimension drawings Marking Design UIMip Physical address 15 15 255 Physical address for tunneling connections 15 15 241 15 15 242 15 15 243 15 15 244 IP configuration IP address assignment DHCP AutoIP IP routing multicast address 224 0 23 12 ...

Page 16: ...t rail TH35 according to IEC60715 Protection type IP20 according to IEC60529 Pollution degree 2 according to IEC60664 1 Protection class III according to IEC61140 Overvoltage category II according to IEC60664 1 Approbation KNX certified according to ISO IEC14543 3 CE Marking According to low voltage and EMC guidelines Compliance EN50428 EN50581 EN61000 6 EN62479 Power supply Safety extra low volta...

Page 17: ...rovided with the distribution 3 The name of the author may not be used to endorse or promote products derived from this software without specific prior written permission THIS SOFTWARE IS PROVIDED BY THE AUTHOR AS IS AND ANY EXPRESS OR IMPLIED WARRANTIES INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE DISCLAIMED IN NO EVENT SHALL THE ...

Page 18: ...the configuration of the IP network please refer to IP Configuration Q I tried to reach the Web front end of my UIMip but I wasn t successful What can I do A Make sure the http matches your device IP along with the port address 8080 Or type the MAC address into the browser s address bar in exactly the way as explained see Via the MAC Address Then wait for about 5 15 seconds refresh your browser an...

Reviews: