REPLACING THE REGULATING SPRING   

 

Disassembly 

 

Close gas inlet valve (V1) located at the inlet to the installation.   

 

Close gas inlet valve (V3) located at the outlet to the regulator. 

 

Open bleed key (V2), located at the outlet to the regulator, until the area is depressurised. 

 

Remove the plastic cover (1) in order to access the regulating nut (2) 

 

Use a 24 mm tube spanner to turn the nut (2) anticlockwise and remove it. 

 

Remove the regulating spring. 

 

Installation 

 

Choose from the list below the most suitable regulating spring for the required outlet pressure.  

 

Carry out the operations described under "disassembly" in reverse order. It should be borne in mind that only those 
screws indicated in the table below should be fitted. The fitting of other springs could cause damage to the regulator. 

 

TOOLS FOR MAINTAINING THE R-120.../B REGULATOR

 

 

 

 
 

Open-ended spanner  

00 – 00 - 00

 

 

        

 

 

10 x 1.6 screwdriver 

 
 

 

 

Tweezers 

   

    

 

 
 
     Hexagonal tube spanner  
             00 - 00  - 00 

 

                                                      OUTLET PRESSURE ADJUSTMENT SPRINGS / VES 

Wd (regulation) 

 

Wrv (differential with regard to Pd) 

 Version 

Spring code 

Adjustment 

fiel

in mbar 

 

 Version 

Spring code 

Spring range 

in mbar 

R-120ES 

ZM3.00.000000 

150 to 300 

 

R-120ES 

ZM3.00.000000 

000 a 000 

R-120ES 

ZM3.00.000000

 

250 to 600 

 

R-120ES 

ZM3.00.000000

 

000 to 000

 

R-120ES 

ZM3.00.000000

 

400 to 800 

 

R-120HP 

ZM3.00.000000

 

000 to 000

 

R-120HP 

ZM3.00.000000

 

700 to 1800 

 

R-120HP 

ZM3.00.000000

 

000 to 000

 

R-120HP 

ZM3.00.000000

 

    1600 to 4000   

R-120HP 

ZM3.00.000000

 

000 to 000

 

   

VIS MAXIMUM/MINIMUM ADJUSTMENT SPRINGS 

Wdo (maximum) 

Spring code 

Adjustment field 

in mbar 

ZM3.00.000000 

000 to 000 

ZM3.00.000000

 

000 to 000

 

ZM3.00.000000

 

000 to 000

 

ZM3.00.000000

 

000 to 000

 

ZM3.00.000000

 

000 to 000

 

ZM3.00.000000 

000 to 000

 

 

Wdu (minimum) 

Spring code 

Adjustment field 

in mbar 

ZM3.00.000000 

000 to 000 

ZM3.00.000000

 

000 to 000

 

ZM3.00.000000

 

000 to 000

 

ZM3.00.000000

 

000 to 000

 

       
 
   

APQ SA

   Crtra. Ripollet 51 P.Ind. Foinvasa  T.0034 935 647 550    F.0034 935 647 211  E-mail  

[email protected]

   website apq.cc                    

 

Technical Features 

 
bpu             1÷20 bar                     (inlet pressure range) 
Ps                   20 bar                     (design pressure) 
Pu                   20 bar                   (maximum inlet pressure) 
Wd                                    (outlet pressure regulating 
range) 
R-120 ES    150 ÷   800 mbar 
R-120 HP    600 ÷ 4000 mbar 
Wdo            300 ÷ 6000 mbar          (maximum safety 
range) 
Wdo            100 ÷ 2500 mbar          (minimum safety 
range) 
Wrv             +10 ÷ +30% Pd                (VES firing range) 
Ac               20 %                (degree of regulating pressure) 
Sg               30 % máx.               (degree of regulating 
pressure)  
 T               -20ºC ÷ 60ºC       (operating temperature) 
 
Inlet connection  

 

1” Gas thread 

Outlet connection    

1” Gas thread 

Connection layout  Axial 
Weight R-120 ES 

 

2 – 2.5 kg 

Weight R-120 HP 

 

2.5 – 3 kg 

 

Summary of Contents for R-120 HP

Page 1: ...talling the regulator ensure that The regulator selected see label coincides with the needs of the installation The fluid passes through the body of the regulator in the correct direction as indicated on the arrow on the body of the regulator The tubing has been previously clean and the gas reaches the regulator perfectly clean and dry The regulator must positioned so that there is sufficient room...

Page 2: ...sh opening the shutoff valve V1 slowly located at the filter inlet F1 Slowly finish opening the shutoff valve V3 located downstream from the regulator Close the bleed valve V2 The time required to press down the button opening the internal bypass will depend on the differential of pressure between the inlet and outlet and the volume of the outlet tank ADJUSTMENTS Regulators are supplied with sprin...

Page 3: ...he necessary adjustments at the inspection hole 9 Regulator with VIS at maximum Make the adjustments described above Connect an external source of pressure via the bleed valve V2 in the tank located along the stretch between the outlet to the regulator R and the outlet valve V3 Slightly increase the pressure in the tank until you see that the VIS maximum pressure valve is activated If it is necess...

Page 4: ... 000000 000 a 000 R 120ES ZM3 00 000000 250 to 600 R 120ES ZM3 00 000000 000 to 000 R 120ES ZM3 00 000000 400 to 800 R 120HP ZM3 00 000000 000 to 000 R 120HP ZM3 00 000000 700 to 1800 R 120HP ZM3 00 000000 000 to 000 R 120HP ZM3 00 000000 1600 to 4000 R 120HP ZM3 00 000000 000 to 000 VIS MAXIMUM MINIMUM ADJUSTMENT SPRINGS Wdo maximum Spring code Adjustment field in mbar ZM3 00 000000 000 to 000 ZM...

Reviews: