A final module screen is displayed showing which specific modules were initialized.
The controller then displays the lamp optimization screen for 60 seconds to allow the lamp to
reach its optimum output. Finally, a final “start-up complete” screen is displayed. The system will
now be ready to disinfect water flow.
all detected modules
lamp reaching max output
successful start-up
UV-SPH-P Operational Screens
On systems without the UV monitor, the default screen shows the Home Screen. At any point
during operation the user is able to scroll through the Home Screen, Lamp life remaining, QR
Code, Contact Info and Maintenance Parts screens by pressing the button located on the front
of the controller.
On systems with the UV monitor, the system will display the same screens as on the UV-SPH-P
except the UV Intensity replaces the home screen. The UV Intensity screen displays the level of
UV light detected by the sensor. UV intensity can be affected by poor water quality, scaling on
the quartz sleeve and/or sensor, lamp failure or lamp expiring. The following screens show the
UV Intensity dropping.
Below 56%, the numbers and warning sign turn red and an audible chirp is given by the ballast
every 15 seconds. Below 51%, the screen is solid red and a constant audible alarm is given. This
alternates with a screen indicating “water may be unsafe for consumption”. With the solenoid
module, the controller de-activates the solenoid valve, shutting off all water flow.