• Refit the lid to the backbox, using the supplied screws.
.
6
5
+
Unsupervised relay
switch output
WIRING EXAMPLE FOR THE RELAY SWITCH OUTPUT
• Ensure the device connected to the unit is not drawing
more than 2 A at 30V (no 220 VAC). Drawing too much
current through the output relay or connecting mains
voltage could possibly damage the unit and void warranty.
Note: install a properly fire-rated cable (according
to national code of practice) between the third-party
device and the output module.
R
EOL
Supervised relay switch
output (needs polarised load)
V
EXTERNAL
DEVICE
- +
- +
- +
- +
port B
input
port A
output
power supply
V
+
External
device
R
EOL
WIRING EXAMPLE FOR 100MA/12 VDC OR 50 MA/24
VDC EXTERNAL DEVICE DRIVING CAPABILITY
• The 10KΩ R resistor monitors whether the cable
has been damaged or the connection is no longer available.
• If you fail to install these resistors correctly the device will
not operate as intended.
- +
- +
R
EOL
R
EOL
10 KΩ
external
device
- +
- +
EOL
R
EOL
10 KΩ
RW1700-052APO
REACH Output Module
QUICK START GUIDE
Apollo Fire Detectors Ltd. 36 Brookside Road, Havant, Hampshire, United Kingdom, PO9 1JR
T: +44 (0)23 9244 2706 - E: techsales@apollo-fire.com - W: www.apollo-fire.co.uk
RW_QSG_MODULE_OUTPUT_REV_A.1