INSTALLING ORBIS

Orbis has been designed to make 

installation fast and simple.  Fig 4 shows 

the TimeSaver mounting base as it is seen 

from the installer’s point of view.
The E-Z fit fixing holes are shaped to allow 

a simple three-step mounting procedure:

• Fit two screws to the mounting box 

or surface

• Place the Orbis base over the 

screws and slide home

• Tighten the screws

The base offers two fixing centres at 51 

and 60mm.
A guide on the base interior indicates 

the length of cable to be stripped.  Five 

terminals are provided for the cables, 

four being grouped together for ease of 

termination. 
The terminals are:

• positive IN
• positive OUT
• negative IN and OUT (common 

terminal)

• remote LED negative connection
• functional earth (screen)

The terminal screws are captive screws 

and will not fall out of the terminals.  

The base is supplied with the screws 

unscrewed in order to avoid unnecessary 

work for the installer.
The end-of-line resistor or active device 

should be connected between the OUT+ 

and COM– terminals.
If it is required that all detectors be fitted 

with their LEDs facing the same direction 

the bases must be fitted to the ceiling 

observing the marking on the exterior 

which indicates the position of the LED. 
The bases may be connected as shown in 

Fig 5 where remote LEDs, if required, are 

connected to the associated base.
Fig 6 shows how to connect one remote 

LED to more than one base so that an 

alarm in any of the detectors connected 

will switch the remote LED. 

In many installations bases with diodes 

are specified in order that an active end-

of-line device may be fitted. Diode bases 

are marked ‘OD’. Loop continuity testing 

is facilitated as there is a continuity device 

in the base. The continuity device enables 

power to pass through every base in a loop 

to ensure that each is connected correctly.
Once a detector is fitted to the base the 

continuity device is automatically locked 

permanently open so that the power flows 

through the detectors.    

FITTING ORBIS 

DETECTOR HEADS

When the bases have been installed and 

the system wiring tested, the detector 

circuits can be populated.

Two methods are suggested:
1.  Apply power and fit the detectors one 

by one, starting at the base nearest 

the panel and working towards the 

end of the circuit. As each detector 

is powered up it will enter ‘StartUp’ 

and flash red (see next page for a 

full description of this feature).  If the 

LED does not flash, check the wiring 

polarity on the base and ensure there 

is power across IN+ and COM–. If the 

LED is flashing yellow the detector 

is not operating correctly and may 

require maintenance or replacing 

(see DirtAlert and SensAlert® below 

and the section ‘Maintenance and 

servicing’ on page 15). 

2. Fit all detectors to the circuit, apply 

power and check detectors by 

observing the LED status of each 

device. The StartUp feature lasts for 

4 minutes so it may be necessary to 

reset or de-power the circuit to allow 

all detectors to be observed. The LED 

status is the same as method 1.

Table 2

Product Description

Base 

Marking 

Code

Orbis TimeSaver Base

OB

Orbis TimeSaver LX Base

OL

Orbis TimeSaver Diode Base

OD

Orbis TimeSaver Relay Base

OR

Savwire Base

OS

TimeSaver Diode Base LX

DX

Orbis LX Base

XL

Orbis Timesaver Base - Deep

EB

Orbis Heater Base

HB

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for ORB-HT-11001-APO

Page 1: ...www apollo fire co uk ORBIS PRODUCT GUIDE Optical Detector Multisensor Detector Heat Detector Mounting Bases www acornfiresecurity com www acornfiresecurity com...

Page 2: ...ORBIS 2 conventional detectors from Apollo www acornfiresecurity com www acornfiresecurity com...

Page 3: ...etectors work 11 Environmental performance 11 Technical Data 11 Orbis TimeSaver Base 12 Installing Orbis 12 Fitting Orbis detector heads 13 Orbis Features LED Status 13 TimeSaver LX 14 Relay Base 14 S...

Page 4: ...f Orbis is to make installation commissioning and maintenance quicker enhance the reliability of detection and reduce the incidence of false alarms Orbis features TimeSaver Base designed for fast inst...

Page 5: ...st which is an m value of 2 The performance of Orbis detectors is given as a solid line which shows how evenly the optical detectors respond to the test fires If detectors respond too quickly the lowe...

Page 6: ...onfirmation of smoke before the alarm signal given The algorithms are used to verify signals from the sensing chamber to filter out transients and to decide when the detector should change to the alar...

Page 7: ...LED 1 2k connected to negative supply characteristic MECHANICAL Material Detector and base moulded in white polycarbonate Alarm Indicator Integral indicator with 360 visibility See Table 3 on page 13...

Page 8: ...ms The multisensor smoke detector has two sensors one for smoke one for heat and the alarm decision is derived from either sensor or a combination of both The multisensor is a development of the Orbis...

Page 9: ...ts 40mA Alarm load 600 Holding voltage 5 33V Minimum holding current 8mA Minimum voltage to light 5V alarm LED Alarm reset voltage 1V Alarm reset time 1 second Remote output LED 1 2k connected to nega...

Page 10: ...es heat detectors according to the highest ambient temperature in which they can safely be used without risk of false alarm The classes are identified by the letters A to G Class A is subdivided into...

Page 11: ...acteristics and the choice of the right type for a particular application may not always seem straightforward It is helpful to understand the way that heat detectors are classified as explained earlie...

Page 12: ...many installations bases with diodes are specified in order that an active end of line device may be fitted Diode bases are marked OD Loop continuity testing is facilitated as there is a continuity d...

Page 13: ...ors are wired in the correct polarity Flashes once per second No Flash FasTest Maintenance procedure takes just 4 seconds to functionally test and confirm detectors are functioning correctly Flashes o...

Page 14: ...Number ORB BA 10008 APO LED COM IN O U T 1 2 3 4 LED COM IN O U T 1 2 3 4 _ To next detector From control panel Screen Functional Earth Screen Functional Earth COM COM N C N C N O N O RELAY CONTROLLED...

Page 15: ...pplied to the detector If this is the case the LED will flash red once a second StartUp will not check whether the IN and OUT connections have been transposed This is not a problem if standard bases a...

Page 16: ...PP2147 2010 Issue 4 Apollo Fire Detectors Ltd 2003 2010 www acornfiresecurity com www acornfiresecurity com...

Reviews: