22
System Wiring
© 2011 Apollo Security Inc.
IP Address: IP address of the ENI-100. This is a static IP address so the network administrator
must verify that it will not be used elsewhere in the system.
Telnet Enable: When checked, enables Telnet access to the web page and configuration files
stored in the ENI.
Telnet Password: Password that must be entered to log in the Telnet server in the ENI. NOTE:
No user name is used for Telnet access.
WWW Enable: When checked, enables web page access for configuring the ENI.
WWW Username and Password: User name and password that must be entered to access the
configuration via the web page.
Baud Rate: The baud rate that the ENI will use to communicate on the serial port. This setting
must match the baud rate of the programming host. Required: 9600
ENI Port: The TCP port number that must be used to open a network connection to the ENI.
This should be an unused port on your network. Consult your system administrator for more
information. Recommended: 3001 - must match setting in software
WWW Port: The HTTP port that the web server will use to display the configuration pages. The
default value is 80 which is used by default by most web browsers. If it is necessary to set
another port, it will be necessary to specify the port when accessing the configuration page. For
example, if port 8080 were used, it would be necessary to specify this port in addition to the IP
address such as entering in the browser address bar: http://192.168.10.177:8080.
Connection: Select either a TCP or UDP connection. TCP communication is used for AAN-1/2
to host communication. Required: TCP
Connection Parameters
(The following settings should not be used with the AAN-1/2)
Host IP Address/Port: When auto-connect is enabled, this is the first host address of another
ENI device which a connection will be established with. Set all values to '0' to disable this
feature. Required: Not enabled
Auto Connect: If checked will cause the ENI to automatically connect to the Host Address
given. This address should be another ENI that is not set to auto connect. Required: Not
enabled.
Gateway Address and Subnet Mask: These are used to connect to another ENI that is not on
the same network when the Auto Connect box is checked. Set all values to '0' to disable this
feature. Required: Not enabled.
UDP HOST LIST
From the main screen clicking the “UDP Host List Button” will display the Host List configuration. This feature
is not used by the ENI-100 when used with the AAN-1/2.
After changing any of the above configuration options, click the “program” button at the bottom of the page.
The ENI will then save the settings and will be reset. Clicking the “Reset” button at the bottom of the page
will reset the values to their current configuration. If you do not wish to change any configuration options,
simply close the browser window without pressing either button.
Summary of Contents for AAN-1
Page 6: ...Part Introduction I ...
Page 10: ...Part Hardware Layout II ...
Page 19: ...Part System Wiring III ...
Page 43: ...Part Software Configuration Utilities IV ...
Page 53: ...Part Troubleshooting V ...
Page 56: ...Part Specifications VI ...
Page 58: ...Part Supplemental Figures VII ...
Page 59: ...54 Supplemental Figures 2011 Apollo Security Inc 7 Supplemental Figures ...
Page 60: ...55 AAN 1 AAN 2 Hardware Manual 2011 Apollo Security Inc ...
Page 61: ...56 Supplemental Figures 2011 Apollo Security Inc ...
Page 62: ...57 AAN 1 AAN 2 Hardware Manual 2011 Apollo Security Inc ...
Page 63: ...58 Supplemental Figures 2011 Apollo Security Inc ...
Page 64: ...59 AAN 1 AAN 2 Hardware Manual 2011 Apollo Security Inc ...
Page 65: ...Part Table of Figures VIII ...
Page 67: ...Part Revision History IX ...