7. Measure the distance from the bottom of the stem to the new actuation point.
The actuation point is at the center position between the float stops. In the
example above, the actuation point is at 250 mm.
8. A brass rod inside the stem holds the reed switches in place. The location of
the switch needs to be adjusted to match the new actuation point. Determine
which switch type you are using and continue to the step indicated below.
NOTE: The float is considered in the “normal” position when it is at
rest against the lower stop.
CODE “A & B” (approx. 20 mm switch length)
CODE “C” (approx. 30 mm switch length)
Normally Open continue to step 8a
(page 15)
Normally Closed skip to step 8b
(page 16)
Normally Open skip to step 8c
(page 17)
Normally Closed skip to step 8d
(page 18)