8. W

ATER

 

METERS

8.1. C

HOOSING

 

THE

 

RIGHT

 

WATER

 

METER

 

SIZE

The main criterior for choosing the right water meter size (nominal diameter) should always be the water
meter working conditions, that is the average and maximum value of a passing water working flow.

When a water meter is too large, it does not increase the investment cost, but also has lower accuracy in
case of small water flow. A too small water meter can cause its overload and sumiltaneously quicken the
wear of its active parts.

It is recommended to choose the size of the water meter so that the size of the largest expected jet flow in
the system between 0,45 and 0,6 of the water meter constant jet flow Q

3

.

8.2. W

ATER

 

METER

 JS

8.2.1. Single jet dry type water meter

Single jet dry type water meter consists of two basic units: measurement unit and counting mechanism. The
main elements of the measurement unit are: a body with a sieve places in an inlet channel, a vane, a sealing
plate.  Main  components of  a counting mechanism  are:  a gear set,  a roll set  and a counter  cover.  The
mechanism is attached to the unit by means of fastening ring and after legalisation, sealed with lead.

Single jet water meter vane is propelled by a jet of water which pushes ifs blades along the vane perimeter
and it is the only movable element submerged in water. Rotor rotation is conveyed by a magnetic head
clutch, through the sealing plate. Dry counter, sealed air-tight in separete module, sums the flow of measured
water and displays the result in digital, easy to read manner. Counter is fitted with a motion detector which
makes it possible to automate regulation and legalisation. 

The   regulating   device   is   protected   from   tampering   by  a   lead   seal.  Thanks   to   a   special   design   of   rotor
bearings and the choice of corrosion and abrasion resistant materials, the water meter is characterised by
high durability.

8.2.2. Parameters

Type

cold water

             

warm water

JS-1,6

JS90-1,6

JS-2,5

JS90-2,5

JS-2,5-G1

JS90-2,5-G1

JS-4

JS90-4

Nominal diameter

[mm]

15

20

 Permanent flow rate Q

3

[m

3

/h]

1,6

2,5

4

Overload flow rate Q

4

[m

3

/h]

2

3,125

5

Minimum flow rate Q

1

(horizontal / vertical installation)

[dm

3

/h]

16 / 32

20 / 40

25 / 50

31,25 / 62,5

40 / 80

50 / 100

Transition flow rate Q

2

(horizontal / vertical installation)

[dm

3

/h]

25,6 / 51,2

32 / 64

40 / 80

50 / 100

64 / 128

80 / 160

Maximum permissible error
(Q

2

 to Q

4

)

±2 %

±3 %

Measuring range R (Q

/ Q

1

)

(horizonral / vertical installation)

100 / 50

80 / 40

Max. working temperature

[°C]

30

90

Max. working pressure

1,6 MPa (16 bar)

Lenght

[mm]

110

130

Conformity

MID, EN 14154, OIML R49

*   For   water   meters   DN   15,   Q

3

  =   2,5   m

3

  is   also   possible   to   order   a   water   in   lengh   L=80   or   L=115

(input/output = 

7/8

/

3/4

“ pro L=115)

13 / 17

Summary of Contents for E-RM 30

Page 1: ...RADIO MODULE FOR WATER METER E RM 30 Installation and service manual APATOR METRA s r o Havl kova 919 24 787 64 umperk tel 420 583 718 111 fax 420 583 718 150 e mail prodej metra su cz www http www m...

Page 2: ...mode 9 5 3 2 Switch a radio module to the mode of automatic activation 9 5 3 3 Switch a radio module to the sleeping mode 10 5 4 Electronic seal reactivation 10 6 OTHER INFORMATIONS 10 6 1 Transportin...

Page 3: ...are also used data are read simultaneously Every user can control current value on analogue dial of water meter In contrast to the traditional water meter radio module E RM 30 distinguish the directio...

Page 4: ...dio module is equipped with electronic seals and also the option to use mechanical seals in order to safeguard the module from tampering If there is an unauthorised removal of the module from the mete...

Page 5: ...of measured values including real time Function control automatic Dimensions 70 x 44 x 71 mm Power suply lithium battery 3 V Calculat battery lifetime e g chapter 2 1 Type list Material polycarbonate...

Page 6: ...ion in past billing period back flow consumption in billing period before last standard flow consumption in billing period before last back flow date of electronic seal activation date of electronic s...

Page 7: ...n consists only from putting module on water meter and installation of mechanical seal In mode of automatic activation module regulary tests disc presence If the presence is detected measuring of wate...

Page 8: ...reading unit IRU 10 00 The IRU 10 00 displays information related to the last unit it has read It is therefore necessary to carry out a data reading from the radio module so that you can view the par...

Page 9: ...l mode change is indicated by a single beep and the display showing o Pro 5 An unsuccessful mode change is indicated by four beeps and the display showing E Pro For more informations refer to the Inst...

Page 10: ...adio module is now in working mode and has broken electronic seal 2 Cover optical sensors with black cover used during module trasportation 3 Switch a radio module to the sleeping mode with an infra r...

Page 11: ...ntrary to installation and service manual or damaged during transport or storage by customer or reseller when mounted or dismantled to the customer device because of improper handling or installation...

Page 12: ...E RM 30 Installation and service manual M2016 09f EN 12 17 Illustracion 3 Packing sheet...

Page 13: ...et of water which pushes ifs blades along the vane perimeter and it is the only movable element submerged in water Rotor rotation is conveyed by a magnetic head clutch through the sealing plate Dry co...

Page 14: ...ion notified person number flow direction as an arrow V or H marking for vertical or horizontal pipes or both jet flow value Q3 Q1 andr Q3 ratio marking of measurement unit in m3 on the counter dial v...

Page 15: ...k between a valve and a strraight pipe section and before the water meter 5 For an installation of a water meter which does not cause strain in the body it is recommended to use compensative connector...

Page 16: ...tion and the filter if it is used should be cleaned During flushing use a spigot to replace the water meter 2 Before installation check the operation of a water meter by starting a rotating motion of...

Page 17: ...alternative connector JS 90 2 5 G1 8 3 WATER METER GSD8 RF Nominal flow Qn 1 5 m3 h Maximal flow Qmax 3 m3 h Max working pressure 16 bar Class of accuracy B horizontal installing A vertical installing...