background image

(7-segment display)

Fiber side

Transmission side

ON/OFF threshold display (Green)

Light receiving level display (Red)

-L*F1011  8/11-

Setting for operation mode change

Set if there is a diagnosis mode.

Variable

0

Disabled (Simple mode)

1

Enabled (Normal mode)

Default: 0

- Address writer (ARW-04): Parameter 07

Light ON/Dark ON setting

Set Light ON/Dark ON.

Variable

Details

0

Transmission type dark (shielding) ON

1
2

Reflection type dark (w/o reflection) ON

3

Default: 0

- Address writer (ARW-04): Parameter 06

 Light receiving level display setting

Set the display of the light receiving level.

Variable

0
1

Default: 0

- Address writer (ARW-04): Parameter 08

Transmission type light (transmission) ON

Reflection type light (w/ reflection) ON

Light emitting power setting

Set the light emitting level.

Variable

Details

0

High

1
2

Low

Default: 0

- Address writer (ARW-04): Parameter 09

Middle

AD value display (0 - 4095 Digit)
0 - 100% display

ON Delay setting

Set the ON delay time.

Default: 0

- Address writer (ARW-04): Parameter 10

Variable

0 - 999

100ms

Unit

Set the OFF delay time.

Default: 0

- Address writer (ARW-04): Parameter 11

Variable

0 - 999

100ms

Unit

Set the One Shot time.

Default: 0

- Address writer (ARW-04): Parameter 12

Variable

0 - 999

100ms

Unit

Address/Parameter automatic setting (base unit only)

Automatically set the address and parameter.

Variable

0

Automatic setting disabled

1
2

Automatic setting for parameter only

3

Default: 0

- Address writer (ARW-04): Parameter 17

Automatic setting for address only

Address/Parameter automatic setting

* Linked to base unit's parameters.

“3”

Extension

Extension

Extension

Base

Setting address

“0”

“2”
“1”

Allot

Example) 

For parameter 17 value 1

7-segment display orientation switch setting (base unit only)

Variable

0
1

Default: 0

- Address writer (ARW-04): Parameter 18

Normal display
180° flipped display

0: Normal display

Transmission side

Fiber side

1: 180° flipped display

OFF Delay setting

One Shot setting

Details

Details

Details

Details

For "Parameter 8 variable 0: AD value display" - Displays 

the threshold set in the scope of 0 - 4095.
For "Parameter 8 variable 1: 0 - 100% display" - 

Displays the setting threshold from 0 - 100%, with the 

minimum AD value from teaching as 0 and the maximum 

as 100%.

For "Parameter 8 variable 0: AD value display" - Displays 

the amount of light received converted as an AD value 

set in the scope of 0 - 4095.
For "Parameter 8 variable 1: 0 - 100% displays" - 

Displays the received light from 0 - 100%, with the 

minimum AD value from teaching as 0 and the maximum 

as 100%.

This functional automatically reflects in the extension unit the addresses and 

parameters set in the base unit.

If this automatic setting mode is enabled (value 1, 2, or 3), addresses and 

parameters set to the base unit are automatically alloted to the extension unit.

This function flips the 7-segment display by 180°.

This is convenient when, depending on the orientation of this product, the 

numbers are difficult to read.

Summary of Contents for ASLINKAMP L-F1011 Series

Page 1: ...ion Amplifier body 1 Amplifier body 1 Expansion connector LED display 7 segment display Protective cover Base LED display 7 segment display Protective cover Transmission line L IN K IN A L M L IN K IN...

Page 2: ...th of the transmission line and the supply current Table 1 L F1011 2 11 Connection Example You can select use of either a two wire or four wire terminal for the AnyWireASLINK according to the load cur...

Page 3: ...5A 24V DC Filter of COSEL Co Ltd EAC 06 472 MAX 6A 24V DC Model Type Allowable power current Filter allowable power current Insert the ASLINK filter Type ANF 01 regardless of installation method and d...

Page 4: ...wer supply 24V 0V 24V 0V PE DP DN 24V 0V Four wire terminal DP DN 24V 0V Four wire terminal A B 24V 0V 24V 0V PE Filter notation in the drawing General purpose power supply filter Use if necessary Gen...

Page 5: ...l a separate block If only the LA F1011 and LB F1011 are connected a single system can support up to 128 units Hook movable latch A onto the DIN rail Push down on fixed latch D on the opposite side un...

Page 6: ...details L F1011 6 11 Connect the transmission line of the base unit to the transmission line from the master unit This terminal is a four wire isolated type that is used by connecting to DP DN 24V an...

Page 7: ...efault 50 Address writer ARW 04 Parameter 05 100ms Unit Alarm value monitor time setting Carry out setting with the work actually used 0 100 AD value 0 100 AD value 0 100 AD value 0 100 Setting scope...

Page 8: ...2 Automatic setting for parameter only 3 Default 0 Address writer ARW 04 Parameter 17 Automatic setting for address only Address Parameter automatic setting Linked to base unit s parameters 3 Extensi...

Page 9: ...ddress only Address Parameter automatic setting 0 1 Automatic setting for parameter only Linked to base unit s parameters 0 Address Parameter automatic setting Base unit only 1 2 3 09 0 High Middle 0...

Page 10: ...36 7 72 70 32 7 10 LINK IN ALM 200 10 LB F1011 Extension unit 7 36 7 72 72 32 10 14 25 LINK IN ALM 10 One point input IP40 Number of occupied points 24V 0V 25mA 1 9mA DP DN Consumption current Protec...

Page 11: ...1 Address Anywire Corporation Contact by mail Contact info_e anywire jp Contact by website http www anywire jp Headquarters 1 Babazusho Nagaokakyo shi Kyoto 617 8550 JAPAN Printed in Japan 2016 2017 U...

Reviews: