DiaLog Elite PLC Interface Manual
Analog Inputs
After entering the Register Type (Holding or Input) and Register Number the Elite drops
down into the section that allows entering alarm and channel processing information.
n
n
.
Channel Number [11-98]
0
Channel Conversion
0
Decimal Position [0-5] (
2
)
Zero Scale [0-99999] (
0
)
Full Scale [0-99999] (
10000
)
Zero Sign
[
0
– negative,
1
–
positive
]
1
0
disabled
1
milliamps
2
amps
3
volts
4
degrees Centigrade
5
degrees Fahrenheit
6
gallons
7
liters
8
pounds
9
kilograms
1
0
gallons per minute
1
1
gallons per hour
1
2
million gallons per hour
1
3
liters per hour
1
4
cubic inches per second
1
5
cubic feet per minute
1
6
cubic feet per hour
1
7
pounds per hour
1
8
feet per second
1
9
inches
2
0
feet
2
1
meters
2
2
parts per million
2
3
watts
2
4
kilowatts
2
5
degrees
2
6
pounds per square inch
2
7
percent
2
8
pH
2
9
Hz
3
0
kHz
3
1
mgal
2
Input Type [0-8]
0
0-1V
1
0-5V
2
1-5V
3
0-10V
4
0
-
20ma
5
4-20ma
6
+/- 1V
7
+/- 5V
8
+/- 10V
1
Channel Messages
Alarm message (8 seconds)
Normal message (8 seconds)
2
Channel Mode
0
–
Disabled
1
– Status Only
2
– Call on Alarm
©
Antx, inc. 2001
Version 1.2
11
Summary of Contents for DiaLog Elite
Page 1: ...DiaLog Elite Modbus Master Interface Manual Publish Date August 1 2003 Document Version 1 2 ...
Page 2: ......
Page 4: ......
Page 6: ...DiaLog Elite PLC Interface Manual ii Version 1 2 Antx inc 2001 ...
Page 12: ...DiaLog Elite PLC Interface Manual 2 Version 1 2 Antx inc 2001 ...
Page 16: ......
Page 24: ...DiaLog Elite PLC Interface Manual 14 Version 1 2 Antx inc 2001 ...
Page 28: ...DiaLog Elite User Manual 2000 Antx inc 18 Version 1 2 ...