Low Gas Pressure Models

Low gas pressure switches break the electrical circuit on 

pressure drop at the point when gas pressure becomes 

lower than the indicated set pressure.

Before the manual reset button (Figure 6) can be prop-

erly latched, gas pressure in the chamber must be higher 

than the indicted setting.  The position of the yellow ring, 

on the reset button, shows whether the reset button is on 

or off.  If the yellow ring on the button is below the cover, 

the unit is on (not latched).  If the yellow ring is above 

the cover, the unit is off (latched).  The yellow ring must 

be below the cover after latching to be properly set.

High Gas Pressure Models

High gas pressure switches break the electrical circuit 

when pressure rises above the indicated preset pres-

sure.  The yellow ring will be below the cover, indicating 

that the switch is on, when the gas pressure in the switch 

chamber is below the indicated high setting.  When the 

yellow ring on the reset button is above the cover, it indi-

cates the switch is in the off position, and gas pressure is 

above the indicated setting.

Range Adjustment - All Models

To adjust gas pressure cut-off setting, remove the cover.  

Turn the range scale adjustable knob (Figure 6) clock-

wise to increase pressure setting, counterclockwise to 

decrease pressure setting.  Install cover and tighten the 

two cover screws to prevent tampering.

Figure 6

Figure 1

Figure 5

Figure 2

Figure 3

Figure 4

RANGE SCALE 

(ADJUSTABLE KNOB)

RESET BUTTON

RHGP-G  or RLGP-G

HGP-G  or LGP-G

OPTIONAL SWITCH BASE SIDE 

MOUNTING SUGGESTIONS 

WITH “O” RING

OPtiOnAL

 SWITCH BASE 

SIDE-By-SIDE MOUNTING 

SUGGESTIONS HIGH AND 

LOW GAS PRESSURE

OPTIONAL SWITCH BASE  

BOTTOM MOUNTING  

SUGGESTIONS WITH “O” RING

STANDARD SWITCH BASE 

REMOTE MOUNTING  

SUGGESTIONS

STANDARD SWITCH BASE 

PANEL MOUNTING  

SUGGESTIONS

All switches can be mounted in either horizontal or 

vertical position.  Switches should be reasonably level 

but do not required accurate leveling.

Single gas switch models have a 1/4” N.P.T. (female)  

gas inlet on the standard base.

Piping can be either standard black pipe or  

aluminum tubing.

All switches can be supported by the inlet pipe, but 

optional mounting brackets and bases are available (see 

Figures 1 thru 5 below).

Switches have been factory calibrated and tested for 

leaks.  However, it is recommended that switch, gas pipe 

inlets and connections be soap bubble tested for leaks 

after installation.

Operation

Summary of Contents for G Series

Page 1: ... venting to atmosphere Model G GGI 1010810019 Rev A 05 07 RL Automatic Reset Manual Reset WARNING Read these instructions carefully before attempting to install operate or service this switch Failure to observe safety information and comply with instructions could result in personal injury death and or property damage To avoid electrical shock or damage to equipment disconnect power before install...

Page 2: ...g on Switch Operation Connect to Normally OPEN NO or Normally CLOSED NC Cutaway View of Switch to Show Connection to Ground Connect Separate Ground Wire to Ground as Shown if required by local electrical code CONDUIT CONNECTIONS COM nC nO GROUnD Din COnneCtOR wiRinG Pressure Ratings Adjustable Operating Pressure 5W C to 4 psi different ranges Surge Pressure 15 psi 1 Bar NOTE To avoid initial line ...

Page 3: ...nt All Models To adjust gas pressure cut off setting remove the cover Turn the range scale adjustable knob Figure 6 clock wise to increase pressure setting counterclockwise to decrease pressure setting Install cover and tighten the two cover screws to prevent tampering Figure 6 Figure 1 Figure 5 Figure 2 Figure 3 Figure 4 RANGE SCALE ADJUSTABLE KNOB RESET BUTTON RHGP G or RLGP G HGP G or LGP G Opt...

Page 4: ... Single Unit Hi Pressure RHGP G These part numbers are for standard N P T gas inlet and electrical knockout NOTE For optional NEMA 4 Kit 4 Pin DIN Connector Neon Lamp Indicator or Side Mounting contact Antunes Controls for specific part numbers Optional Contact Antunes Controls NEMA 4 IP 65 Kit available Part No 808000404 4 Pin DIN Connector Neon Lamp Indicator Side Mounting It is understood and a...

Reviews: