Antunes Controls G Series Installation Information Download Page 2

MODEL - G

Electrical Ratings

10A @ 125 VAC 

10A @ 250 VAC 

1/3 HP, 125 & 250 VAC

COM

P

NO

NC

Diagram Shows Pressure

Being Applied To Switch

COM

P

NO

NC

Diagram Shows Pressure

Being Applied To Switch

LOW PRESSURE

When pressure decreases below setpoint

NO opens, NC closes

HIGH PRESSURE

When pressure increases above setpoint

NO closes, NC opens

COM

Ground

NO

NC

1/2" Conduit Nut

Connect to Common (COM)

1/2" Conduit

Attach 1/2" Conduit Fitting
to Switch with 1/2" Conduit Nut

Depending on Switch Operation
Connect to Normally OPEN (NO)
or Normally CLOSED (NC)

Cutaway View of 
Switch to Show 
Connection to Ground

Connect Separate Ground
Wire to Ground      as Shown
(if required by local electrical code)

CONDUIT CONNECTIONS

COM

nC

nO

GROUnD

Din COnneCtOR wiRinG

Pressure Ratings

Adjustable Operating Pressure

.5W.C. to 4 psi (different ranges)

Surge Pressure

15 psi (1 Bar)

NOTE: To avoid initial line fill pressure spikes, unit 

should be placed downstream of the regulator.

Maximum Operating Pressure

6 psi (400 mbar) Automatic Reset 

2 psi (138 mbar) Manual Reset

Ambient Operating Pressure

-40°F to 140°F (-40°C to 60°C)

Field wiring to be rated @ 60°C for maximum 

140°F ambient

Summary of Contents for G Series

Page 1: ... venting to atmosphere Model G GGI 1010810019 Rev A 05 07 RL Automatic Reset Manual Reset WARNING Read these instructions carefully before attempting to install operate or service this switch Failure to observe safety information and comply with instructions could result in personal injury death and or property damage To avoid electrical shock or damage to equipment disconnect power before install...

Page 2: ...g on Switch Operation Connect to Normally OPEN NO or Normally CLOSED NC Cutaway View of Switch to Show Connection to Ground Connect Separate Ground Wire to Ground as Shown if required by local electrical code CONDUIT CONNECTIONS COM nC nO GROUnD Din COnneCtOR wiRinG Pressure Ratings Adjustable Operating Pressure 5W C to 4 psi different ranges Surge Pressure 15 psi 1 Bar NOTE To avoid initial line ...

Page 3: ...nt All Models To adjust gas pressure cut off setting remove the cover Turn the range scale adjustable knob Figure 6 clock wise to increase pressure setting counterclockwise to decrease pressure setting Install cover and tighten the two cover screws to prevent tampering Figure 6 Figure 1 Figure 5 Figure 2 Figure 3 Figure 4 RANGE SCALE ADJUSTABLE KNOB RESET BUTTON RHGP G or RLGP G HGP G or LGP G Opt...

Page 4: ... Single Unit Hi Pressure RHGP G These part numbers are for standard N P T gas inlet and electrical knockout NOTE For optional NEMA 4 Kit 4 Pin DIN Connector Neon Lamp Indicator or Side Mounting contact Antunes Controls for specific part numbers Optional Contact Antunes Controls NEMA 4 IP 65 Kit available Part No 808000404 4 Pin DIN Connector Neon Lamp Indicator Side Mounting It is understood and a...