How to Enter Program Change
Programming
IQ-301 PN 50036:F 10/29/2001
89
For descriptions and options for Holiday Zones, refer to Appendix H “Special Zones”.
Code Type (Zone 98)
Software zone 98 (code type), lets you select one of four code types: March Time,
Temporal, California, or Two Stage. Selection of coding only has an effect if one or
more Notification Appliance Circuits call out zone 98. From the Special Zone Change
screen (Figure 74), you key in 98, to display the Code Type screen. Figure 79 shows a
sample Code Type screen with a code type of March Time.
Figure 79 Code Type Screen
For descriptions and options for Code Types, refer to Appendix H “Special Zones”.
Pre-Alarm (Zone 99)
Use software zone 99 to program the Alert or Action Pre-Alarm. From the Special Zone
Change screen (Figure 74), enter 99 to display the Pre-Alarm screen. Figure 80 shows a
sample Pre-Alarm screen.
Figure 80 Pre-Alarm Screen
For descriptions and options for Pre-Alarm, refer to Appendix G “Pre-Alarm
(AWACS™) Applications”.
3.4.9 How to Edit System Functions (7=
SYS
)
Purpose
You can select global settings for nine system functions, which appear in the System
Function Selection screen. Figure 81 shows a System Function Selection screen with
default values in each system function field. The next section contains descriptions of
each field and contains instructions for editing system functions.
Figure 81 System Function Default Values
Understanding System Functions
This section contains descriptions of the nine system functions, with the field name in
parentheses, and the selections for each function.
"
SIL INH=
Lets you program a Silence Inhibit Timer that disables the Alarm
Silence switch function when a fire alarm occurs. You can enter a timer value between
0-300 seconds or enter 000 for no timer. The timer starts at the first alarm and restarts
with each new alarm.
PRG@SOFTWARE@ZONE
CODE@TYPE:
MARCH@TIME
Z98
PRG PRE-ALARM ZONE
ALERT=70% OF ALARM
ACTION=00% OF ALARM
Z99
Program Change
Password
SIL@INH=000@AUTO=000
VERIFY=00@@@USA@TIME
ANNUN=NON SUPV@@REMT
BLINK=Y@ST=4@AVPS=N