NFPA 72 Proprietary Fire Alarm Systems
NFPA Applications
IQ-301 PN 50036:F 10/29/2001
139
•
If connecting an RPT-485W isolating repeater module between the
AM2020/AFP1010 and the control panel, a common connection between the two
panels is not needed. However—a system common connection must be made from
the AUTOPULSE IQ-301 to RPT-485W,
and
the IQ-301 ground fault jumper JP9
should not be cut.
•
For Receiving Unit installation and programming, refer to the AM2020/AFP1010
manual and the NIB-96 manual.
Figure 135
NFPA 72 Proprietary Fire Alarm Systems
Table 51 Proprietary Fire Alarm Systems Wiring Connections
NIB-96
MPS-24A/
MPS=24AE
TB3
T
B
3
T
B
2
T
B
1
T
B
6
TX REF RX RE F
OU T OUT IN IN
T
B
5
T
B
4
JP8
JP8
JP1
1
1
1
2
2
2
3
3
3
4
4
4
5
5
5
6
6
6
7
7
8
8
AC POWER
FIRE
ALARM
PRE-ALARM
WARNING
SUPERVISORY
SECURITY
ALARM
SILENCED
SYSTEM
TROUBLE
ACKNO WLE DG E
ST EP
ALARM
SILENCE
EVACUATE
HOLD 2 SECONDS
SYS TEM RE SET
IQ-301 Protected
Premises Unit
EIA-485 two-wire loop (Style 4), twisted pair
(power-limited and supervised)
AM2020/AFP1010 Receiving Unit
System
Common
NIB-96
IQ-301
MPS-24A
EIA-485 (+)
P4 Term. 5
TB5 Term. 1
EIA-485 (–)
P4 Term. 3
TB5 Term. 2
System Common
TB1 Term. 6
TB3 Term. 6