Operation
How to Operate the Control Panel
110
IQ-301 PN 50036:F 10/29/2001
A control panel in Fire Alarm operation does the following:
•
Activates the panel sounder with a steady sound.
•
Flashes the F
IRE
A
LARM
LED.
•
Displays a status banner of
ALARM
along with specific information about the
activated device as shown in Figure 104.
•
Latches the device in alarm until the alarm condition is cleared and the system is
reset. Refer to “System Reset” on page 105.
•
Recalculates all Control-by-Event.
•
Starts all timers, such as Silence Inhibit and Auto Silence.
•
Activates the general alarm relay and general alarm zone Z00.
4.3.5 How to Operate a Panel with a Supervisory Condition
What is a Supervisory Condition?
A
Supervisory
is a signal indicating a need to respond to events such as supervision of
a guard tour, a sprinkler, and so on.
How the Panel Indicates a Supervisory
When a supervisory signal occurs, the control panel indicates a supervisory condition.
Figure 104 shows a sample LCD display for a control panel with a supervisory signal.
Figure 105 Sample Display for a Supervisory Signal
A control panel in Supervisory operation does the following:
•
Activates the panel sounder with a warbling tone.
•
Flashes the
SUPERVISORY
LED.
•
Displays a status banner of
ACTIVE
along with specific information about the
activated device as shown in Figure 106.
•
Activates the Supervisory relay.
•
Latches the device until the Supervisory signal is cleared and the system is reset.
Note: In Supervisory operation, the Alarm relay does not activate, silenced alarms do
not resound nor do they reactivate silenced alarm CBE, and timers do not start.
Supervisory signals track and may have their own Control-by-Event. They do not cause
resound of alarms or reactivation of silenced alarm CBE. Supervisory circuits may also
report open circuit troubles, which operate like any other trouble. If the event is a
security point activation, this LED will operate the same as a supervisory, but the LCD
display will show the security type code. Refer to Appendix E for further information
on security alarms.
ACTIVE@TAMPER
SPRINKLER@VALVE@105
FLR@5@MAIN@BUILDING
11:13A@12/25/97@ M37
Label of the first zone
Status banner
ACTIVE
:
Type Code of device sending the
Supervisory signal. For details on Type
Codes, refer to Section 3 “Programming”.
Device activated
Time and date the
device activated
ENTER
ACKNOWLEDGE
STEP
ALARM
SILEN CE
DRILL
HOLD 2 S ECONDS
SYSTEM
RESET
AC POWER
FIRE
ALARM
PRE-ALARM
WARNING
SUPERVISORY
ALARM
SILEN CE
SYSTEM
TROUBLE
D ET
M OD
1
2
3
4
5
6
7
8
9
#
A B C
D E F
G
H
I
J K L
M N O
P R S
T U V
W X Y
Q
Z
- / .
ALL SYSTEMS NORMAL
09:45A THU 06/18/97
Membrne
SUPERVISORY
/
SECURITY
LED flashes
Summary of Contents for AUTOPULSE IQ-301
Page 195: ...IQ 301 PN 50036 F 10 29 2001 195...