![ANEMOI AIRPRO 250 M Installation Manual Download Page 27](http://html1.mh-extra.com/html/anemoi/airpro-250-m/airpro-250-m_installation-manual_2942926027.webp)
AIRPRO [M]
27
6.2
Modbus Installation
6.2.1
Power and Control Connections
The Anemoi Airpro [M] fan with Modbus control must be connected to the power supply with an electrical voltage
of 200-240V (I, 50/60Hz).
The Anemoi Airpro [M] fan needs an external control to work. The external control is connected directly to the fan
control board using shielded cable type Modbus cable RS485 2x2x0.50 mm² POSCY.
The control board fan is located at the top of the mount bracket, the connections and distances are shown below:
PORT DEFINED:
Modbus Control Line
B
White
Negative (-) for data communication
A
Red
Positive (+) for data communication
G
Black
Common for data communication
Motor Line
U
Brown
U-communication for the motor
V
Red
V-communication for the motor
W
Black
W-communication for the motor
Power Line
L
Brown
Power Supply Line
N
Blue
Power Supply Neutral
GND
Green/Yellow
Ground Connexion