background image

COMMISSIONING

SECTION 4

GAS

CONNECTIONS

TO LIGHT 

THE BURNER

TO SHUT OFF

THE BURNER

TO CHECK

MAIN BURNER

PRESSURE

14

CAUTION: DO NOT OPERATE THE WATER HEATER UNTIL THE STORAGE VESSEL IS
COMPLETELY FILLED WITH WATER, WITH WATER RUNNING FROM ALL HOT TAPS.

Open the main gas supply cock after all connections to the gas control thermostat are
complete, and test all connections with soap solution.

1. Remove outer cover wait 3 minutes for any unburnt gas to vent.

2. Turn the gas control knob to pilot. (see below)

3. Fully depress the gas control knob and the piezo ingnitor. With the pilot burner alight,

hold the gas control knob for 20 seconds. When the gas control knob is released the
pilot should remain lit, if not repeat the operation. The pilot can be seen through the
sight glass on the inner cover.

4. Replace outer cover.

5. Set the temperature indication dial to the required temperature. (see below)

6. Turn the gas control knob to ON, the burner should now light, if not repeat the

operation. (see below)

For long periods only, eg. holidays or periods of 7 days or more, turn the gas control
knob to ‘PILOT’ position, depress slightly and turn clockwise to ‘OFF’. Turn off the gas
service cock.

For shorter periods, eg. less than 7 days, leave the heater under the control of the
thermostat.

N.B. If the pilot should become extinguished for any reason, turn off the appliance, and
wait three minutes before attempting to relight.

1. Turn burner OFF as above.
2. Remove brass cap from burner adjustment port. (see below).
3. Release bleed screw A one turn and connect pressure gauge tube.
4. Light burner according to the preceding instructions.
5. Adjust burner pressure at screw B in accordance with data plate. 

Turn screw clockwise to increase pressure and anticlockwise to decrease pressure.

6. Turn burner OFF.  Remove pressure gauge tube and tighten screw A.
7. Replace brass cap in burner pressure adjustment port. (see below).

Thermostat 
Setting

104°F

40°C

125°F

52°C

143°F

62°C

159°F

71°C

Approx. Water
Temperature

Correct size and shape
of the pilot flame

OFF :

PILOT :

ON :

Fig.7 

Lighting Instructions

Note European Symbols:

30 mm

0

1

2

3

Fig. 8 

Burner  Pressure

Adjustment

B

A

Summary of Contents for RSC 150

Page 1: ...as Fired Storage Water Heaters Room Sealed Appliance MODELS RSC 150 RSC 190 INSTALLATION GUIDE OPERATION AND SERVICE MANUAL T H I S M A N U A L M U S T B E K E P T W I T H T H E A P P L I A N C E Part...

Page 2: ......

Page 3: ...on and service on the Andrews Water Heater must be carried out by properly qualified personnel and therefore no liability can be accepted for any damage or malfunction caused as a result of interventi...

Page 4: ......

Page 5: ...ation 6 Water Connections 8 Water Quality Treatment 8 Hydrojet Systems 8 Vented Systems 9 Unvented Systems 10 Gas Connections 13 SECTION 4 COMMISSIONING To Light the Burner 14 To Shut Off the Burner 1...

Page 6: ...GE BS 6700 1997 Specification for design installation testing and maintenance of services supplying water for domestic use within buildings and their curtilages This standard supersedes the following...

Page 7: ...Engineers C1BSE TM13 All Codes of Practice draw attention to the design and operation of water systems with reference to avoidance of factors that favour colonisation by Legionellae bacteria These fa...

Page 8: ...r Heat Output 8 2 kW 27 978 Btu hr 9 4 kW 32 073 Btu hr Gas Flow Rate 0 01 m3 min 0 522 ft3 min 0 02 m3 min 0 577 ft3 min Gas family I2H Natural I2H Natural Flue Gas Temp Approx 180 C 180 C Flue Gas V...

Page 9: ...and an adequate air supply A clearance of 3OOmm l2in should be left around the heater for fitting and servicing purposes and 762mm 3Oin above the heater for removal of the flue baffle The above cleara...

Page 10: ...Fit flue section D2 into heater adaptor D1 4 Fit elbow D4 into flue section D2 for horizontal flue runs 5 Determine correct position of flue outlet and fit outer wall plate and inner wall plate Fit f...

Page 11: ...vers should be so designed that high velocity air streams do not occur within the space housing the heater s IMPORTANT The vapours given off by halogen based compounds can if drawn into the combustion...

Page 12: ...tor light which shows green when the anode is functioning correctly and red if a malfunction occurs Correx UP anodes are available as an optional extra on all models of Andrews storage water heaters a...

Page 13: ...top of the heater Connect the cold water feed and hot water outlet to these nipples with union adaptors for ease of servicing CAUTION DO NOT APPLY HEAT TO THESE NIPPLES IF MAKING CAPILLARY SOLDERED J...

Page 14: ...g Regulations Fig 4 p11 lists and illustrates the component parts of the Unvented Systems Kit Fig 5 p12 illustrates the general arrangement of the components The Wall Mounting Kit is available as an o...

Page 15: ...ing Bush Not shown Tundish Expansion Vessel Wall Mounting Kit Optional Comprises Hose Assembly Wall Bracket Assembly C780 C781 E319 E320 E321 E322 B229 C788 E323 F1 F2 F3 F4 F5 F6 F7 F8 INSTALLATION S...

Page 16: ...mperature Pressure Relief Valve Cold Water Inlet to Water Heater F 2 Check Valve Expansion Valve F 6 Tundish F1 Pressure Reducing Valve Strainer Cold Water Feed Balanced Cold Water Take off if require...

Page 17: ...ed by British Gas p l c or BS 6891 Jointing compound used must conform to BS 6956 Pt 5 CAUTION DO NOT APPLY HEAT IN CLOSE PROXIMITY TO THE GAS CONTROL THERMOSTAT AS THIS WILL RESULT IN DAMAGE OCCURRIN...

Page 18: ...eat the operation see below For long periods only eg holidays or periods of 7 days or more turn the gas control knob to PILOT position depress slightly and turn clockwise to OFF Turn off the gas servi...

Page 19: ...not indicate a leak It will disappear when the storage vessel becomes heated The gas control fitted to this heater has a built in limit thermostat ECO In case of high water temperature the gas supply...

Page 20: ...he burner to gain access to the main jet Remove the main jet and clean with acetone Blow through the main burner with compressed air DO NOT ATTEMPT TO CLEAN ORIFICES WITH SHARP METALLIC OBJECTS IF NEC...

Page 21: ...ess of the original diameter it should be replaced with new Particular attention should be paid to the extreme ends The anode hot outlet nipple can be unscrewed from the top of the heater see page 18...

Page 22: ...already at correct temperature b Replace multifunctional control a Check pilot pipe for loose joints b Check that correct amount of fresh air ventilation is available c Check that flue is clear and i...

Page 23: ...B1 E093 E094 Burner Assembly Comprising items B2 B3 B4 B5 B6 1 B2 E095 E095 Burner Supply Pipe 1 B3 E097 E097 Pilot Supply Pipe 1 B4 C126 C126 Thermocouple 1 B5 E099 E100 Injector 1 B6 E101 E102 Pilot...

Page 24: ...izontal 1 D7 E077 Flue Restrictor 48mm Vertical 1 D7 E078 Flue Restrictor 50mm 1 D7 E107 Flue Restrictor 55mm 1 D8 E065 E065 Flat Roof Plate 1 D9 E066 E066 Angled Roof Plate 1 D10 E105 E105 Horizontal...

Page 25: ...NOTES 21...

Page 26: ...NOTES 22...

Page 27: ......

Page 28: ...Wednesbury One Black Country New Road Wednesbury West Midlands WS10 7NZ Tel 44 0 121 506 7400 Fax 44 0 121 506 7401 Email andrews andrews waterheaters co uk Website www andrewswaterheaters co uk 07 05...

Reviews: