Hardware Installation
ACX 780/781 Installation Guide 39
4. The CPU light on the Power Supply Status Display (inside cabinet)
begins flashing and flashes every .1 sec if all is normal. If the
controller fails a ROM test, the CPU light flashes every .2 sec. If the
controller fails a RAM test, the CPU light flashes every .025 sec. If
the controller fails any other software test, it flashes every .05 sec.
5. The AC_ON light on the front of the cabinet turns on and remains
on as long as the unit is receiving power.
6. The TD light (for Infinet) may not flash at this time. Once you have
set up the Infinet controller in the software and assigned the
controller an ID, the TD light immediately starts flashing to show
data is being transmitted.
7. The RD light (for Infinet) begins flashing only if data is being
received from other controllers on the network. This may not happen
immediately.
8. If any of the nine door outputs is not set to AUTO, the OVERRIDE
light (inside cabinet) remains steadily on.
9. The status lights on the front door of the cabinet, labeled with output
numbers, turn on if the output value is ON (see Figure 24).
Figure 23 shows the status lights inside the cabinet, that also turn on
when the output value is ON.
Reset Button
The RESET button is the small button just to the left of the logo on the
board (near the top). You press it to restart the controller without eras-
ing memory. The same events occur as described above.