![Andover Controls ACX 780 Installation Manual Download Page 38](http://html1.mh-extra.com/html/andover-controls/acx-780/acx-780_installation-manual_2942440038.webp)
Hardware Installation
32 Andover Controls Corporation
3. Slip the other end of the +5 wire under the +5 V screw on the
controller and tighten the screw down on it.
4. Slip the other end of the LED wire under the LED screw and tighten
the screw down on it.
5. Slip the other end of the DATA wire under the 1/DATA screw on
the controller and tighten the screw down on it.
6. Slip the other end of the CLK wire under the 0/CLK screw on the
controller and tighten the screw down on it.
7. Slip the other end of the COMMON wire under the GND screw and
tighten the screw down on it.
Figure 18 illustrates where you connect the various wires.
Figure 18. Wiring Dorado ABA Card Reader to Controller
8. Tie back the shield as well as any wires you do not use.
If you would like to connect a different card reader, contact your An-
dover Controls representative.
For information on how to assign and program the inputs and outputs,
see the Infinity CX or SX 8000 Programmer’s Guide.
+5V
LED
DATA
CLK
COMMON
GND
0/CLK
1/DATA
LED
+5V
Card Reader
ACX 780/781
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com