3/4" MNPT X 3/4" SLIP FIT

PVC RIGID PIPE

FLEXIBLE TUBE

CONSTANT DOWNWARD

SLOPE 1/8"/FT (MIN.)

3/4" MNPT X 3/4" SLIP FIT

PVC RIGID PIPE

FLEXIBLE TUBE

CONSTANT DOWNWARD

SLOPE 1/8"/FT (MIN.)

CONSTANT DOWNWARD

SLOPE 1/8"/FT (MIN.)

KEEP TOP OF 

LOOP BELOW THE 

BOTTOMOF THE 

DEHUMIDIFIER

CABLE TIE

DRAIN TRAP

3/4" MNPT x 3/4" 

BARB

3/4" FEMALE PIPE 

x 3/4" FNPT

PRIME TRAP

3/4" MNPT x 3/4" BARB

3/4" MNPT x 3/4" 

FEMALE PIPE

3/4" MNPT x 3/4" 

FEMALE PIPE

FLEXIBLE TUBE

FLEXIBLE TUBE

PVC 

RIGID PIPE

DRAIN TRAP

DRAIN TRAP

CONSTANT DOWNWARD

SLOPE 1/8"/FT (MIN.)

KEEP TOP OF 

LOOP BELOW THE 

BOTTOMOF THE 

DEHUMIDIFIER

CABLE TIE

DRAIN TRAP

3/4" MNPT x 3/4" 

BARB

3/4" FEMALE PIPE 

x 3/4" FNPT

PRIME TRAP

3/4" MNPT x 3/4" BARB

3/4" MNPT x 3/4" 

FEMALE PIPE

3/4" MNPT x 3/4" 

FEMALE PIPE

FLEXIBLE TUBE

FLEXIBLE TUBE

PVC 

RIGID PIPE

DRAIN TRAP

DRAIN TRAP

CONSTANT DOWNWARD

SLOPE 1/8"/FT (MIN.)

KEEP TOP OF 

LOOP BELOW THE 

BOTTOMOF THE 

DEHUMIDIFIER

CABLE TIE

DRAIN TRAP

3/4" MNPT x 3/4" 

BARB

3/4" FEMALE PIPE 

x 3/4" FNPT

PRIME TRAP

3/4" MNPT x 3/4" BARB

3/4" MNPT x 3/4" 

FEMALE PIPE

3/4" MNPT x 3/4" 

FEMALE PIPE

FLEXIBLE TUBE

FLEXIBLE TUBE

PVC 

RIGID PIPE

DRAIN TRAP

DRAIN TRAP

+ - A B ODT

Sensor

Remote

Gh
Rf
Cf
Gs

Y

W

HV

AC E

QUIP
.

DH

DH

R/+

C/-

B

A

MODEL A77 CONTROL

90-2479

90-2479

90-2479

90-2479

90-2479

90-2481

90-2480

5A. DRAIN CONNECTIONS – A210V1

5B. DRAIN CONNECTIONS – A320V1/V3

DO NOT DOUBLE TRAP

6. WIRING 

•  Mount control at canopy height.

•  Do not mount in direct path of 

dehumidifier outlet air.

•  Shield control from lights.

anden.com 

P.O. Box 1467 
Madison, WI 53701-1467 
800.972.3710  F: 608.257.4357 
Printed in USA
©2019 

Anden – A Quality brand from Research Products Corporation

10013947 B2208490A 4.19

7. SET-UP & SEQUENCE OF OPERATION WITH MODEL A77

1. 

Plug unit in and turn power switch to ON.

2. 

The on-board control screen should display OFF.

90-1854

NOTE:

 The first button press will only turn on the 

backlight. 

3. 

Hold the MODE button on the on-board control for 
3 seconds to enter the Installer Set-up Menu.

90-1854

8. CODES 

(LOCATED ON BACK OF WIRE ACCESS COVER)

See the Installation Instructions for troubleshooting 
error codes. For additional assistance, Technical 
Support is available Monday through Friday, 7:00 a.m. 
to 5:00 p.m. CST, at (800) 972-3710.

Contact Technical Support before replacing the unit 
or components and for additional troubleshooting.

SEQUENCE OF OPERATION

1. 

At the Model A77, press the ON button; the Model A77 will display the measured RH and ON.

2. 

Use the UP or DOWN button on the Model A77 to adjust the humidity setting as desired. 

3. 

If the RH measured by the Model A77 rises above the setting, the dehumidifier will turn on. “DEHUMIDIFYING” 
will appear on the dehumidifier control display and ON will blink on the Model A77 to show that there is a call for 
dehumidification. The dehumidifier will turn off when the RH measured by the Model A77 drops 3% RH below the setting.

NOTE:

 When using the Model A77, there is an initial 3 minute delay at power-up before the dehumidifier compressor will 

turn on.

4. 

Press the UP or DOWN button to change to ENABLED.

90-1854

5. 

Press MODE repeatedly until DONE shows on screen.

90-1854

6. 

Press ON/OFF to turn ON.

90-1854

ERROR CODE

FAILURE MODE

E1

Internal %RH/ Temperature Sensor Failure

E2

High Refrigeration Pressure

E3

Model 76 Remote Control Communication Loss

E4

Insufficient Capacity

E5

High Temperature Thermistor Failure

E6

Low Temperature Thermistor Failure

E7

Float Switch Open

E8

Inlet Air Temperature Out of Range

A320V1

12/3,6-20P

A320V3

12/3,L7-20P

A210V1

14/3,6-15P