background image

 

 

3

INSTALLATION 

 

MOUNTING 

 
Mount the unit in a DRY location.  Allow at least 4 inches of clearance around it for adequate cooling. 
 

POWER CONNECTION 

 
The unit is supplied with a 5 foot power cable.  This should normally be adequate to connect to a 
source of power.  If you must extend the power cable be sure to use a 3 conductor grounded type 
extension cable.  For hard wiring to a source of power, cut off the plug, and strip the wires as 
necessary.  The wire colours are 
 

110 VAC 

220 VAC 

Black - AC Hot 

Black - Phase 1 

White – AC Neutral

White - Phase 2 

Green – Ground 

Green – Ground 

 
All connections should be made inside an appropriate junction box.  The maximum current draw from 
a 110 VAC source is 8.1 amps, so a 10 amp circuit breaker should be used in the circuit panel.  For a 
220 VAC source, 4 amps is the maximum current draw, so a 5 amp circuit breaker should be used in 
the circuit panel to feed power to the PWS610. 

 

OUTPUT CONNECTIONS 

 
Two Positive output terminals and two Negative output terminals are provided.  Connect only one wire 
to each terminal.  Ensure that the total average load connected does not exceed the continuous 
current rating of the unit.  
 

LOAD SHARE OPTION 

 
The units may be configured for load sharing if they are equiped with the optional output isolation 
diodes.  To confirm that your unit has these diodes, use an ohmmeter to measure the resistance 

between the two positive output terminals.  If the diodes are present the terminals will measure as not 
connected.  If the diodes are NOT present, the terminals will measure as a short circuit.  Assuming 
the output isolation diodes are present, connect one 4 foot piece of #12 AWG red wire to each 
positive output terminal.  Connect all the positive wires to a distribution bus, or connect them together, 
and then connect from the common point to the load using the correct gauge of wire for the total 
output capability of all the supplies running in parallel.  Repeat this process for the negative terminals 
using the same gauges of wire, but black in colour.  These units should now load share.  You can 
confirm this by watching the output ammeters.  A slight difference is negligable, however, if this is not 

OUTPUT 1

OUTPUT 1

OUTPUT 2

OUTPUT 2

Summary of Contents for PWS610 Series

Page 1: ...PWS610 Series Power Supply Installation Operation Manual ...

Page 2: ...and ordinances DANGER Never alter AC cord or plug provided if it will not fit outlet have proper cord installed by a qualified electrician Improper connection can result in a risk of an electric shock Analytic Systems does not recommend the use of the PWS610 Series Power Supplies in life support applications where failure or malfunction of this product can be reasonably expected to cause failure o...

Page 3: ... Input Fuse MDA 12 6 Output Voltages Nominal op 12Vdc 24Vdc 48Vdc Actual 13 6 0 05Vdc 27 2 0 05Vdc 54 4 0 10Vdc Adjust 0 5 Output Crowbar 16 0 0 5 Vdc 32 0 1 0 Vdc 63 9 2 0 Vdc Output Amps cont 40 20 10 Output Amps max 45 25 12 5 Transient Response 1 V for 30A 1 V for 20A 1 V for 9 5A General Input Frequency 45 65 Hz Noise on Input 50 milli Volts Noise on Output 50 milli Volts Efficiency 80 maximu...

Page 4: ...ovided Connect only one wire to each terminal Ensure that the total average load connected does not exceed the continuous current rating of the unit LOAD SHARE OPTION The units may be configured for load sharing if they are equiped with the optional output isolation diodes To confirm that your unit has these diodes use an ohmmeter to measure the resistance between the two positive output terminals...

Page 5: ...current into each of the output terminals 1 ammeter and 1 voltmeter allow monitoring of total output current and output voltage TROUBLE SHOOTING This unit provides LED indicators and a buzzer to help diagnose any problems The unit should sound the buzzer to alert you prior to shutting itself down You should immediately check the indicators to determine the cause of the shutdown LOW OUTPUT Indicate...

Page 6: ... off the unit and move the jumper to the other position on J22 J22 is located next to the relay To change the position of the jumper first turn the unit off and disconnect the unit from both the power and batteries Next turn the unit on for 30 seconds to discharge the capacitors then turn it off again Turn the unit upside down and remove the four screws Remove the cover and locate J22 It will be n...

Page 7: ...OL A remote control panel may be connected to the power supply using a 9 pin D connector that attaches to the side of the power supply The remote control panel and D connector are part of the remote control option The remote control panel allows the unit to be operated remotely as well as duplicating all the diagnostic indicators and audible alarm ...

Page 8: ...o remedy the defect after having a reasonable number of opportunities to do so 5 Warranty service shall be performed only by the Warrantor Any attempt to remedy the defect by anyone else shall render this warranty void 6 There shall be no warranty for defects or damages caused by faulty installation or hook up abuse or misuse of the equipment including exposure to excessive heat salt or fresh wate...

Reviews: