Operation
Turn the switch on the side of the unit on to energize the outputs. The green indicator light
will glow to indicate the proper operation of the unit.
All connections should be made inside an appropriate junction box. The maximum current
draw from the 110 VAC supply is 16.2 amps, so a 20 amp circuit breaker should be used in the
circuit panel and for a 220 VAC supply, 8.1 amps is the maximum current draw, so a 10 amp
circuit breaker should be used in the circuit panel to feed power to the power supply.
OUTPUT POWER CONNECTION
The unit’s output is equipped with a 4 pin socket. The pin configuration on the output connec-
tor is as follows:
Pin A, C
Positive
Pin B, D
Negative
If the load exceeds the continuous rating for too long a period, the temperature sensor inside
the unit will turn off the output. After the unit cools sufficiently, it will automatically come
back on. If this happens frequently, remount the unit for increased airflow so it cools better.
WARNING
:
This unit has no reverse output hook up protection or output fusing. If the output is hooked up
in reverse, the unit may be damaged or destroyed.