Installation Guide

NI-900 

NetLinx Integrated Controller

The NI-900 (FG2105-90) is designed to control and automate a variety of devices in single rooms or 
multiple small rooms and is capable of supporting devices with a variety of communication formats. It 
is configured to control a limited number of lights, thermostats, video displays and other equipment. 

ATTENTION!

Verify you are using the latest version of NetLinx Studio (available for download from 
www.amx.com).

       

Port Assignment and Functionality

Ethernet Ports Used By the NI Controller  

Note

: While the NI-900 is capable of receiving 8 and 9 bit characters, it cannot receive 7 bit, 1 stop 

bit data from a serial device (ex: 9600,N,7,1).

RACK MOUNT SAFETY INSTRUCTIONS

If installed in a closed or multi-unit rack assembly, the operating ambient temperature of the 

rack environment may be greater than room ambient. Therefore, consideration should be 
given to installing the equipment in an environment compatible with the maximum ambient 
temperature 50°C.

Installation of the equipment in a rack should be such that the amount of air flow required for 

safe operation of the equipment is not compromised.

Mounting of the equipment in the rack should be such that a hazardous condition is not 

achieved due to uneven mechanical loading.

Consideration should be given to the connection of the equipment to the supply circuit and the 

effect that overloading of the circuits might have on over current protection and supply wiring. 

Reliable earthing of rack-mounted equipment should be maintained. Particular attention 

should be given to supply connections other than direct connections to the branch circuit (e.g. 
use of power strips).

FIG. 1  

NI-900

NI-900 Specifications

Dimensions (HWD):

• 1 9/16" x 5 9/16" x 5 1/8" (4.01 cm x 14.10 cm x 13 cm)
• RU:  1

Power Requirement:

• 300 mA @ 12 VDC

• Power requirements are usage dependant

Memory:

• 64 MB SDRAM 

(not upgradeable)

• 32 MB Flash chip 

(not upgradeable)

• 512 Kb of Non-volatile SRAM

Microprocessor:

• 304 MIPS

Weight:

• 1.30 lbs (0.59 kg)

Enclosure:

• Metal with black matte finish

Certifications:

• FCC Part 15 Class B, CE, and IEC 60950

Front Panel Components

PROGRAM Port:

RS-232 DB9 connector (male) can be connected to a DB9 port on a PC. 
This port can be used with both Serial and NetLinx commands.

CONFIGURATION
 DIP Switch:

8-position DIP Switch sets the communication parameters for the 
Program port.

IR RX LED (red): 

Lights when IR data is being received via the rear IR RX port.

IR LEDs (red): 

Light during the transmission of IR or Serial data via the 3 rear IR ports.

I/O LEDs (yellow): 

Light when the rear I/O channels 1 - 4 are active. LED indicator for each 
I/O port reflects the state of that particular port.

SERIAL LEDs 
(red and yellow): 

Light when the rear DB9 Port transmits or receives RS-232/422/485 
data.

Note

: These LEDs do not reflect changes in either the RTS or CTS when 

hardware handshaking is used.

MASTER LEDs

• LINK/ACT (green): Lights when the Ethernet cable is connected and 

an active link is established. This LED also blinks when receiving 
Ethernet data packets.

• Status (green): Lights when the Controller is programmed and 

communicating properly.

• Output (red): Lights when the Controller transmits data, sets channels 

On and Off, sends data strings, etc.

• Input (yellow): Lights when the Controller receives data from button 

pushes, strings, commands, channel levels, etc.

ID Pushbutton: 

Sets the NetLinx ID (Device only) assignment for the device.

Rear Panel Components

RS-232/422/485 
(Port 1): 

RS-232/422/485 control port uses a DB9 (male) connector with XON/
XOFF (transmit On/transmit Off), CTS/RTS (clear to send/ready to send), 
and 300 - 115,200 baud.

IR RX (Port 6):

4-pin 3.5 mm mini-Phoenix port is used to connect up to 8 IRX-SM+ 
swivel mount or IRX-DM+ Decora mount IR receivers. 

Note

: The IR RX port functions using AMX IR codes (38 KHz and 455 

KHz) and works ONLY with AMX IR Receivers such as the IRX-DM+ and 
IRX-SM+.

I/O (Port 5):

4-channel digital I/O port for contact closure with each input being 
capable of voltage sensing. Input format is software selectable with
interactive power sensing for IR ports.

Note

: The I/Os are not dry closure; they are electronic switches that float 

at 5V when Off. Therefore, they should not be expected to work in 
situations that require true dry contact (or dry closure). The I/Os do work 
with AMX PC1, PC2, UPC20 and UPC20+. 

IR (Ports 2-4)

IR/Serial control ports support high-frequency carriers of up to 1.142 
MHz with each output being capable of three electrical formats: IR, 
Serial, Data. 2 IR/Serial data signals can be generated simultaneously.

Note

: IR ports support data mode (at limited baud rates and wiring 

distances).

PROGRAM port (DB9)

CONFIGURATION DIP Switch

IR RX LED

MASTER Status LEDs

SERIAL Status LEDs

I/O Status LEDs

IR Status LED

ID Pushbutton

PORT 1 (RS-232/422/485)

ETHERNET 10/100 Port (RJ45)

12VDC Power connector

IR RX connector

I/O connectors

IR connectors

AxLink connector / LED

(front)

(rear)

NI-900 Specifications (Cont.)

Rear Panel Components

AxLink Port/LED: 

4-pin 3.5 mm mini-Phoenix (male) connector provides data and power to 
external control devices.
Green AxLink LED indicates the status of the port.

ETHERNET 
10/100 Port: 

RJ-45 port for 10/100 Mbps communication. LEDs show communication 
activity, connection status, speeds, and mode information:

SPD (speed)

 - Yellow LED lights On when the connection speed is 100 

Mbps and turns Off when the speed is 10 Mbps.

L/A (link/activity)

 - Green LED lights On when the Ethernet cables are 

connected and terminated correctly, and blinks when receiving 
Ethernet data packets.

12VDC PWR:

Power Port: 2-pin 3.5 mm mini-Phoenix (male) connector.

Operating 
Environment:

• Operating Temperature: 0° C (32° F) to 50° C (122° F)
• Operating Humidity: 20% - 85% RH
• Heat Dissipation (Typical): 12.3 BTU/hr

Included 
Accessories:

• 2-pin 3.5 mm mini-Phoenix female PWR connector (41-5025)
• 6-pin 3.5 mm mini-Phoenix female I/O connector (41-5063)
• Three CC-NIRC IR Emitters
• Two 4-pin 3.5 mm mini-Phoenix female connectors (41-5047)

Other AMX 
Equipment: 

• AC-RK Accessory Rack Kit (FG515)
• CC-NIRC IR cables (FG10-000-11)
• CC-NSER IR/Serial cable (FG10-007-10)
• IRX-PP38 Plasma Proof IR Sensor (FG460)
• IRX-DM+ IR Sensor (FG458-10 and FG458-11)
• IRX-SM+ IR Sensor (FG455-01)
• PMB Pole Mount Bracket (FG531)
• STS, Serial To Screw Terminal (FG959) 
• Surface Mount Bracket Accessory (FG525)

NI-900 Port Assignments

Port

ICSP Port #

Serial Port #1

1

IR/Serial Port #1

2

IR/Serial Port #2

3

IR/Serial Port #3

4

I/O Port

5

IR RX Port

6

Ethernet Port Usage

Port type

Description

Standard Port #

FTP

The on-board Master has a built-in FTP server.

21/20 (TCP)

SSH

The SSH port functions using the same interface as Telnet but 
over a secure shell where it uses SSL as a mechanism to con-
figure and diagnose a NetLinx system. 

Note

: Only SSH version 2 is supported.

22 (TCP)

Telnet

The NetLinx Telnet server provides a mechanism to configure 
and diagnose a NetLinx system.

 23 (TCP)

HTTP

The Master has a built-in web server that complies with the 
HTTP 1.0 specification and supports all of the required 
features of HTTP v1.1. This port is used for unsecure HTTP 
Internet communication between the web browser’s UI and the 
target Master.

80 (TCP)

HTTPS/SSL This port is used by a web browser to securely communicate 

between the web server UI and the target Master. 

443 (TCP)

ICSP

Peer-to-peer protocol used for both Master-to-Master and 
Master-to-device communications.

1319 (UDP/TCP)

integration!
Solutions

This feature on the Master uses, by default, port 10500 for the 
XML based communication protocol. This port is connected to 
by the client web browser’s JVM when integration! Solutions 
control pages are retrieved from the on-board Master’s web 
server. 

10500 (TCP)