background image

Installation

THIS PRODUCT MUST BE INSTALLED 

BY A LICENSED PROFESSIONAL.

 1.

  Be sure to have a complete bladder kit (bladder kit consists of 

blind flange, bladder support pipe and bladder assembly).

 

2.

  Isolate tank from system.

 

3.

  Drain water from bladder.

 

4.

  Remove air valve core to bleed remaining air charge.

 

5.

  Remove drain plug. (Figure 1).

 

6.

 Disconnect system connection.

 

7.

  Unbolt blind flange from tank and pull out bladder kit from 

tank. (Figure 2).

 

8.

 Wash down inside walls of tank as necessary.

 

9.

 Mop up remaining water.

10.

  Dry out inside of tank (reversed vacuum cleaner or air line 

from compressor).

11. 

Clean out any remaining dirt.

12.

  Examine interior of tank for any rust blisters and remove them.

13.

 Fold new bladder around bladder support pipe. (Figure 3).

14.

  Insert new bladder kit into bottom of tank. 

Use existing bolts 

from tank flange. 

(Figure 4).

15.

  Using water from spray bottle, lubricate bladder to make it 

easier to fit through flange opening. (Figure 5).

Figure 1

Figure 2

Figure 3

Figure 4

Figure 5

PLEASE READ THE FOLLOWING INSTRUCTIONS CAREFULLY

IMPORTANT GENERAL SAFETY INFORMATION - 

ADDITIONAL SPECIFIC SAFETY ALERTS APPEAR IN THE FOLLOWING INSTRUCTIONS.