FAILURE TO PROPERLY SEAL THE VALVE CAP WILL 

RESULT IN LOSS OF PRECHARGE CAUSING 

PRODUCT TO FAIL

.

Installation

THIS PRODUCT MUST BE INSTALLED BY A 

LICENSED PROFESSIONAL.

1. Visually inspect THERM-X-TROL

 

for any damage. If damage 

exists return product for replacement.

2. With tank empty of water, adjust pre-charge to match cold 

water supply pressure.

Failure to follow these instructions could result in damage 

to the bladder or diaphragm and void all warranties.

3. Replace and tighten plastic cap on air stem.
4. Therm-X-Trol Deep Drawn(-DD) only: Insert Turbulator

  

into connector.

5.  Install the THERM-X-TROL

 

on the city supply line to the 

water heater at a point between the water heater and 

backflow preventer, check valve or pressure reducing valve 

(see Figure 1). Mount vertically only.

6.  Once the THERM-X-TROL

 

 is installed, check the city supply 

line for any leakage. Make repairs if necessary.

7.  Before the initial firing of the water heater, open any hot 

water fixture and draw water until all air is removed from the 

system. Turn the water heater temperature control to desired 

ending temperature level, (see water heater instructions).

8.  To relieve initial thermal expansion, slightly open a hot water 

faucet. Continue until water heater aquastat temperature is 

satisfied. Once heater is at its operating range, no further 

bleeding of expanded water is required.

9.  The system water heater and THERM-X-TROL

 

will now 

be operational.  The THERM-X-TROL

 

will control pressure 

increases caused by thermal expansion to a level well below 

the water heater relief valve setting.

Maintenance

1.  A licensed professional should check the complete heating 

system, including the THERM-X-TROL, yearly and more 

frequently as the system ages.

Operation

1.  The THERM-X-TROL

 

 is installed in the supply line between 

the backflow preventer and the water heater. Its sealed-in air 

pre-charge prevents water from entering it until the system 

pressure exceeds the pre-charge pressure.

2.  As the water temperature rises, expanded water enters 

the THERM-X-TROL’s non-corrosive water reservoir. The 

pre-charged air chamber absorbs the pressure increase, 

keeping system pressures below the relief valve setting.

3.  As hot water is used, the pressure in the air chamber forces 

water back into the system until the THERM-X-TROL is 

empty. At this point, the pressure in the air chamber once 

again equals the supply pressure.

4.  Water temperature is not to exceed 200° F or fall below 35° F.

NOTE:

  Models are listed (ST-5C through ST-210VC) under 

ASME Section VIII, Division I.

Warranty

ST-5C through ST-210VC Models

: One (1) Year Limited Warranty

Visit www.amtrol.com for complete warranty details.

Figure 1. Typical Installation

PLEASE READ THE FOLLOWING INSTRUCTIONS CAREFULLY

IMPORTANT GENERAL SAFETY INFORMATION - 

ADDITIONAL SPECIFIC SAFETY ALERTS APPEAR IN THE FOLLOWING INSTRUCTIONS.

THERM-X-TROL

Expansion Tank

CWS

BFP, Check or PRV

Hot Water

T & P

Valve

Water

Heater

Backflow Preventor, Check Valve 

or Pressure Reducing Valve

Turbulator

 Installation (ST-5C-DD & ST-20VC-DD only)

Thermal 

Expansion

Tank

In-Line

Models

Stand

Models

Cold

Water

Supply

Hot Water

T & P

Relief

Valve

Water

Heater

ST-20VC

Press Turbulator fully 

into connector prior 

to installing tank.

Turbulator

Tank Connector

Turbulator

 Installation 

Deep Drawn (DD) Models Only

© 2019 Worthington Industries Inc. 

Part #: 9017-091 (01/19)

One or more features of this product are covered by U.S. patents, visit www.amtrol.com/patents for more information.

1400 Division Road, West Warwick, RI  USA 02893

T: 800.426.8765  

www.amtrol.com

LOW-LEAD

Reviews: