Pre-Installation

1  Visually inspect for any damage. Ensure expansion tank is sized 

properly for application (Figure 1).

2.  Remove plastic cap from air valve.
3. With tank empty of water, adjust air precharge to match system fill  

pressure.

4.  Replace and tighten plastic cap on air valve.

FAILURE TO PROPERLY SEAL VALVE CAP 

WILL RESULT IN LOSS OF PRECHARGE 

CAUSING PRODUCT TO FAIL.

Mount tank vertically in downward position only. 

Ensure the piping can support the entire weight 

of the tank when full of water.

 

Models SX-30V through SX-160V are floor 

standing and may not be hung from the piping.

 

Do not install the EXTROL on a dead-end pipe 

or wherever air can collect. This can cause 

corrosion and possible leakage.

Installation

1. Drain the boiler system or isolate the area where the EXTROL will  

be installed.

2.  Install the EXTROL on the supply side of the boiler, on the suction-side 

of the heating circulator(s) (Figure 2).

3.  Pressurize the system and check for leaks. Repair as necessary.
4.  Restart the boiler system and check for relief valve discharge. If the 

relief valve drips, the tank may be improperly charged or undersized.

5. The EXTROL is now operational and will absorb expanded water 

during boiler operation.

Maintenance

A professional plumber should check the complete system, 

including the expansion tank, yearly and more frequently as the 

system ages. Checking the precharge allows a small quantity of 

air to escape and can result in an insufficient air charge. Always 

check the precharge while the tank is isolated and empty of water, 

and be sure to maintain the proper precharge whenever the tank  

is inspected.

Warranty

EX Models: Five (5) Year Limited Warranty 
SX Models: One (1) Year Limited Warranty

Visit www.amtrol.com for complete warranty details.

Figure 1.

Figure 2.

Boiler

Net Output in 

1000’s of BTU

Type of Radiation and Piping System

Finned Tube 

Baseboard or Radiant 

Panels with Series 

Loop System

Convectors or 

Unit Heaters 

with One Pipe 

System

Radiators  

or  

One Pipe 

System

Cast Iron 

Radiators 

with Series 

Loop System

200

SX- 30V

SX-30V

SX-30V

SX-30V

250

SX- 30V

SX-30V

SX-30V

SX-40V

300

SX- 30V

SX-30V

SX-40V

SX-40V

350

SX-30V

SX-30V

SX-40V

SX-60V

400

SX-30V

SX-40V

SX-60V

SX-60V

450 

SX-40V

SX-40V

SX-90V

SX-90V

500

SX-40V

SX-40V

SX-60V

SX-90V

550

SX-40V

SX-60V

SX-60V

SX-90V

600

SX-40V

SX-60V

SX-90V

SX-90V

650

SX-60V

SX-60V

SX-90V

SX-90V

700

SX-60V

SX-60V

SX-90V

SX-90V

750

SX-60V

SX-60V

SX-90V

SX-110V

800

SX-60V

SX-90V

SX-90V

SX-110V

850

SX-60V

SX-90V

SX-90V

SX-110V

900

SX-60V

SX-90V

SX-110V

SX-110V

950

SX-90V

SX-90V

SX-110V

SX-110V

1,000 

SX-90V

SX-90V

SX-110V

SX-110V

1,100

SX-90V

SX-90V

SX-110V

SX-130V

1,200

SX-90V

SX-90V

SX-110V

SX-130V

1,300

SX-90V

SX-110V

SX-130V

SX-160V

1,400

SX-110V

SX-130V

SX-160V

SX-160V

1,500

SX-110V

SX-130V

SX-160V

(2)SX-110V

Sizing based on: Average Boiler Water Volume; Average Water Volume;

Fill Pressure 12 psig; Relief Pressure 30 psig

Air

Separator

System

Supply

Flow-Check

Valve

Circulator

Air Vent

Extrol

Expansion

Tank

Relief

Valve

System

Return

Shut-Off

Valve

Water

Supply

Pressure-

Reducing

Valve

Shut-Off

Valve

System

Purge

Backflow

Preventer

Boiler

System

Supply

Flow-Check

Valve

Circulator

Air

Purger

Air Vent

Extrol

Expansion

Tank

Relief

Valve

Boiler

System

Return

Shut-Off

Valve

Water

Supply

Pressure-

Reducing

Valve

Shut-Off

Valve

System

Purge

Backflow

Preventer

Boiler

Net Output

in 1000’S

of BTU/Hr.

Type of Radiation

Finned Tube

Baseboard or 

Radiant Panel

Convectors

or Unit

Heaters

Radiators

Cast Iron

Baseboard

Cast Iron

25

EX-15

EX-15

EX-15

EX-15

50

EX-15

EX-15

EX-30

EX-30

75

EX-30

EX-30

EX-30

EX-60

100

EX-30

EX-30

EX-60

EX-60

125

EX-30

EX-60

EX-60

EX-90

150

EX-30

EX-60

EX-90

EX-90

175

EX-60

EX-60

SX-30V

SX-30V

200

EX-60

EX-60

SX-30V

SX-30V

250

EX-60

EX-90

SX-30V

SX-40V

300

EX-90

SX-30V

SX-30V

SX-40V

350

SX-30V

SX-30V

SX-40V

SX-60V

400

SX-30V

SX-40V

SX-40V

SX-60V

Sizi

ng based on: 12 psig Fill; 30 psig Relief Valve; 200°F Average Temperature.

In-Line Models: 

EX-15 through EX-90

Stand Models:

SX-30V through SX-160V

PLEASE READ THE FOLLOWING INSTRUCTIONS CAREFULLY FOR

IMPORTANT GENERAL SAFETY INFORMATION AND ADDITIONAL SPECIFIC SAFETY ALERTS.

VISIT www.amtrol.com TO VIEW HELPFUL VIDEOS

.