6. READY-TO-RUN RTR-SERIES
PIPING INSTALLATION
DOMESTIC WATER PIPING
1. Connect the cold water supply to the pipe labeled COLD
WATER.
2. Connect the HOT WATER piping to the domestic hot water
system.
3. Make an 8-inch “heat trap” on the HOT WATER outlet as
shown in the diagram. This will reduce standby losses from
heat migrating up the piping.
4. When all domestic water piping is complete, open the cold
water supply and allow some water to enter the tank. Look
and listen for signs of leaks and repair as necessary before
continuing.
Note: If installing on a city supply, ensure a dedicated
Thermal Expansion tank (Therm-X-Trol
®
or equivalent) is
used.
5. Install a blowdown tube on the T&P relief valve outlet.
Plumb to within 6 inches above a floor drain or as directed
by plumbing code.
BOILER PIPING
1. Plumb the BOILER SUPPLY line. The circulator and flow
check are factory installed
2. Pipe the BOILER RETURN connection to the boiler return
line.
Be sure the return line is NOT
plumbed to the suction side of any
heating circulators. This may require moving the
heating circulator off the boiler tapping on packaged
boilers. Failure to do so will result in overheating and
tank damage when the heating system is in
operation.
3. After completing the boiler piping, slowly open the boiler fill
valve and pressurize the heat exchanger loop. Check for
leaks and repair as necessary. Proceed to the appropriate
wiring section in this manual.
If installing on city water supply a
properly sized THERM-X-TROL
®
is
required with the BoilerMate
®
and should be installed as set
forth in the THERM-X-TROL
®
product installation manual.
TOP VIEW
CIRCULATOR
BOILER SUPPLY
BOILER RETURN
SIDE VIEW
DRAIN VALVE
T&P RELIEF VALVE
OUTLET
HOT WATER OUTLET
COLD WATER INLET
LEFT SIDE . . . . . . . . . . . . 1”
RIGHT SIDE . . . . . . . . . . . 1”
TOP . . . . . . . . . . . . . . . . . 9”
REAR . . . . . . . . . . . . . . . . 1”
FLOOR . . . . . . . . . . . . . . . 0”
FRONT . . . . . . . . . . . . . . . 1”
Clearance From Combustible Surfaces
LEFT . . . . . . . . . . . . . . . . . 12”
RIGHT. . . . . . . . . . . . . . . . 12”
FRONT . . . . . . . . . . . . . . . 30”
HEAD ROOM . . . . . . . . . . 36”
REAR . . . . . . . . . . . . . . . . 1”
Recommended Clearance For Servicing