MAINTENANCE AND TROUBLESHOOTING 

 

GENERAL 

7.1

Trained personnel should perform maintenance. A refrigeration technician should be used 
for any servicing of the refrigeration system. An electrician can service the electrical system. 
The balance of the system can most likely be serviced by either.  

To gain access to the system, remove the side covers by removing the screws at the bottom 
of the panels. After removing the screws on the side, slide the panels downward and 
remove. To charge the system with Freon, remove both front and rear panels. The suction 
service valve is located on the front side, on compressor. The discharge service valve is 
located on the rear side, on the accumulator.  

To charge or check Freon pressure, remove service valve covers, attach refrigerant gauges, 
crack service valves. To add Freon, attach Freon bottle and use standard charging 
procedures.  

To check or set the high temperature limit controller, operate the unit in the heat mode with 
the chamber internal conditioning unit shut off. Monitor supply thermometer on front panel or 
place a calibrated thermometer in the reservoir and monitor the fluid temperature. Unit 
should shut off at approximately 110

o

 F. If unit does not shut off at the correct temperature 

adjust the high temperature limit controller, (located on the upper level, front left side of the 
reservoir). An easy way to adjust the controller is to note the present setting of the controller 
and the point at which the heater did shut off and adjust accordingly. Example: The unit shut 
off at 100

o

  F and the controller is set at 105

o

  F, the difference between the actual and the 

desired is 10

o

  F, therefore  it will be necessary to raise the actual set point by 10

o

  F. Set 

temperature controller to 115

o

 F and check the results. 

The low temperature limit controller is set in the same manner. Allow the unit to operate until 
the compressor shuts off and check the temperature. Adjust the controller, heat the unit up 
slightly and run another test to check the set point. 

The cool circuit has a second controller to stop the system in the event of loss of Freon. This 
is the low-pressure controller mounted on top of the compressor electrical junction box. This 
controller will also act as a low limit controller. 

To adjust the time delay for the compressor, remove the cover from the electrical control 
box. NOTE: Removing the cover exposes voltages that are hazards to life, this should only 
be attempted by personnel qualified to work on electrical equipment. The time delay is 
located in the upper left corner of the box. 

Turn clockwise to increase delay time. Check by starting a cycle and timing the time for the 
cool contactor to pull in. 

To check internal fuses, disconnect power from system, remove cover from power control 
box, remove fuses one at a time and check continuity. Replace blown fuses with fuse of 
same value. If fuse blows a second time remove power and determine cause. 

 

 

Summary of Contents for 9000-ECS

Page 1: ...760 599 3857 Email sales amronintl com Web www amronintl com This manual and the information contained herein are provided for use as an operation and maintenance guide No license or rights to manufac...

Page 2: ......

Page 3: ...N 6 GENERAL 6 4 1 REFRIGERATION 6 4 2 FLUID SYSTEM 7 4 3 ELECTRICAL SYSTEM 8 4 4 5 INSTALLATION 9 LOCATION 9 5 1 ELECTRICAL 9 5 2 6 OPERATION 10 7 MAINTENANCE AND TROUBLESHOOTING 11 GENERAL 11 7 1 TRO...

Page 4: ...i 9 PARTS LIST GENERAL 25 9000 ECS ENVIRONMENTAL CONDITIONING SYSTEMS 26 9 1 9000 400 RESERVOIR SUB ASSEMBLY 27 9 2 9000 500 ELECTRICAL SUB ASSEMBLY 28 9 3 AC 5C MD 230V CIRCULATING PUMP 1 8 HP 230V 2...

Page 5: ...ts ranging in size from 54 inch through 72 inch diameters There are certain conditions where the heat load may exceed the capacity of the unit These conditions may occur when the chamber is being pres...

Page 6: ...120 o C Accuracy 1 of Full Scale Refrigerant Compressor Sealed Unit Refrigerant Freon R 404A Protection Internal Thermal Overload Locked Rotor Current 45 Amps Nominal Current Draw 6 4 Amps Restart Int...

Page 7: ...MODEL 9000 ECS USER MANUAL 9000 ECS UM REV 4 0 3 MODEL 9000 ECS 1 3...

Page 8: ...4 2 OPTIONS Model 9000 RCS Remote control switch allows remote control of the Model 9000 ECS The 25 foot remote control cable connects to the remote control connector on the Model 9000 ECS and permit...

Page 9: ...C RETURN THERMOMETER 3 4 Three inch dial dual scale thermometer reads fluid temperature returning to the system Temperature range 0 o to 250 o F 20 o to 120 o C FLUID LEVEL INDICATOR 3 5 Slight glass...

Page 10: ...ts of a fluid system reservoir pump to store and circulate the water a refrigeration unit to cool the water a heater to heat the water and controls to select the mode of operation Internal temperature...

Page 11: ...circuit achieves a balanced condition when the spring force of the expansion valve refrigerant pressure temperature and evaporator pressure temperature results in the proper flow of Freon achieving t...

Page 12: ...ase 50 60 Hz The unit requires a 15 amp fused circuit preferably from a separate disconnect box located close to the system The heater and pump have separate internal fuses The heater is fused at 15 a...

Page 13: ...t be connected via a quick disconnect box with 15 amp fuses Power requirements are 220 VAC 50 60 Hz single phase Voltage limits are 187 to 250 VAC this allows the unit to operate on either a 220 or 20...

Page 14: ...there will be a delay of approximately 45 seconds before the compressor starts This allows the pressures within the compressor to bleed off permitting easier starting and eliminates nuisance blowing...

Page 15: ...eservoir An easy way to adjust the controller is to note the present setting of the controller and the point at which the heater did shut off and adjust accordingly Example The unit shut off at 100 o...

Page 16: ...Cause Unit does not cool Check Freon charge Unit does not run Check power to unit Unit does not run power OK Check fuses to pump Unit does not run power OK fuses OK Check for 24 VAC Unit will not hea...

Page 17: ...following drawings illustrate the electrical and mechanical details of the External Conditioning System unit The drawings reference identifier numbers correspond to the parts list identifier numbers...

Page 18: ...MODEL 9000 ECS USER MANUAL 9000 ECS UM REV 4 0 14 MODEL 9000 ECS SPECIFICATIONS 8 1...

Page 19: ...MODEL 9000 ECS USER MANUAL 9000 ECS UM REV 4 0 15 CHAMBER CONDITIONING CONNECTION DIAGRAM 8 2...

Page 20: ...MODEL 9000 ECS USER MANUAL 9000 ECS UM REV 4 0 16 9000 ECS BLOCK DIAGRAM 8 3...

Page 21: ...MODEL 9000 ECS USER MANUAL 9000 ECS UM REV 4 0 17 ELECTRICAL SCHEMATIC 8 4...

Page 22: ...MODEL 9000 ECS USER MANUAL 9000 ECS UM REV 4 0 18 REMOTE CONTROL WIRING DIAGRAM 8 5...

Page 23: ...MODEL 9000 ECS USER MANUAL 9000 ECS UM REV 4 0 19 PARTS LOCATOR EXTERIOR 8 6...

Page 24: ...MODEL 9000 ECS USER MANUAL 9000 ECS UM REV 4 0 20 PARTS LOCATOR FRONT VIEW 8 7...

Page 25: ...MODEL 9000 ECS USER MANUAL 9000 ECS UM REV 4 0 21 PARTS LOCATOR REAR VIEW 8 8...

Page 26: ...MODEL 9000 ECS USER MANUAL 9000 ECS UM REV 4 0 22 PARTS LOCATOR TOP VIEW 8 9...

Page 27: ...MODEL 9000 ECS USER MANUAL 9000 ECS UM REV 4 0 23 PARTS LOCATOR ELECTRICAL CONTROL BOX 8 10...

Page 28: ...MODEL 9000 ECS USER MANUAL 9000 ECS UM REV 4 0 24 PARTS LOCATOR CIRCULATING PUMP PN AC 5C MD 230V 8 11...

Page 29: ...er Replacement Parts Contact Amron International Inc 1380 Aspen Way Vista California 92081 U S A Telephone 760 208 6500 Fax 760 599 3857 Email sales amronintl com Web www amronintl com When ordering r...

Page 30: ...D 16 0512 100 Tubing Braid reinforced 3 4 I D NS 125HBL 10 8 Hose Barb to male pipe brass NS 125HBL 12 12 Hose Barb to male pipe brass 19 129HB 12 12 Hose Barb 90 elbow to male pipe 20 PTR B 1 X 3 4 P...

Page 31: ...Union 5 8 Brass 42 ECEB4X1 5 Elect Conduit Ext Box 4 X 1 5 43 3219 Grommet 230 546 dia Hole NS ECNP1 2X4 Elect Conduit Nipple 1 2 X 4 NS ECEL1 2 Elect Conduit Ell 1 2M 1 2F 46 A19ABC 4 Thermostat 50 T...

Page 32: ...ontactor DPDT 24 VAC 62 S84Z 401 Transformer 24 VAC 40VA NS 9000 021 Cover Junction Box 64 9000 019 Bracket Electrical Connection 55 9000 018 Plate Junction Box Mounting 65 SO 14 3 Cableso Type14 AWG3...

Page 33: ...Cover 4 O ring Buna N 4A O Ring Vito 5 Ceramic Thrust Washer 7 Spindle 8 Impeller magnet Assembly 8A Impeller Magnet Assembly W Stainless Cover 8B Impeller Magnet Assembly W Bronze Bushing 8C Impeller...

Page 34: ...ccident repair or alterations SERVICE POLICY For technical assistance or to request a repair please complete one of the following Amron Communicator Repair https www amronintl com communicator repair...

Reviews: