CURRENT HARMONICS THEORY
True-RMS current is very important because it directly relates to the amount of
heat dissipated in wiring, transformers, and loads. Most clamp-on meters
already in the field measure average current, not true RMS current, even if
this average value is displayed on a scale calibrated in RMS. These average-
sensing meters are accurate only for sinusoidal signals.
All current signals are distorted in some way. The most common is harmonic
distortion caused by non-linear loads such as office machines, medical equip-
ment, personal computers, or speed controls for motors. Harmonic distortion
causes significant currents at frequencies that are odd multiples of the power
line frequency. Harmonic current can cause a substantial load on the neutral
wires of wye-connected power distribution systems.
In most countries, 50Hz or 60Hz power distribution systems include 3-phase
delta primary - wye secondary transformers. The secondary generally pro-
vides 120V AC from phase to neutral, and 208V AC from phase to phase.
Historically, balancing the loads on each phase was a big headache for the
electrical system designer.
Typically, the vector addition of the phase currents in the transformers' neutral
wire is zero or quite low in a wellbalanced system. Typical devices that pres-
ent linear loading include incandescent lighting and small motors. The result is
essentially a sine wave current in each phase and a low neutral current at a
frequency of 5OHz: or 60Hz.
Devices such as TV sets, fluorescent lighting, video machines, and microwave
ovens are now commonly drawing power line current for only a fraction of
each cycle so that they cause non-linear loading and subsequent
51
Summary of Contents for ACDC-620T
Page 12: ...11 Figure 2 LCD Display ...
Page 31: ...Figure 17 Measuring AC Current CORRECT INCORRECT 30 ...
Page 33: ...Figure 18 Measuring AC Curreft 32 ...
Page 35: ...Figure 19 Measuring AC Motor Curent 34 ...
Page 37: ...Figure 20 Measuring Voltage 36 ...
Page 39: ...Figura 21 Measuring Resistance and Continuity FUSE CARTRIDGE 38 ...
Page 41: ...Figure 22 Surface Temperature Measurement 40 Press Shift ...
Page 45: ...Figure 24 CAPACITANCEMEASUREMENTS 44 Negro Rojo ...
Page 63: ...62 Figure 26 step 1 of Battery replacement Pull up slightly ...
Page 64: ...63 Figure 27 Step 2 of Battery Replacement Pull and move to right ...