Amphenol Wilcoxon TN14 Troubleshooting Installations Download Page 5

Sometimes spurious spikes from fast thermal shifts, lightning strikes, and shocks can overload the sensor 

and cause a momentary shift in the bias voltage. The shift in bias can trigger alarms and protection system 

shutdown devices. To prevent triggering alarms and shutdown, a longer delay can usually be programmed or 

hardwired into the monitoring system. The delay prevents the system from taking action until the sensor has 

settled.

High frequency, high amplitude vibration signals can also overload the sensor and in severe cases cause bias 

shift and erratic time waveform.  However, overload problems are usually detected by observing truncated 

waveforms and large ski-slope spectrums.  

Truncated time waveform: sensor overload

 

Truncated (flattened) time waveforms indicate that the signal is clipping. Clipping causes the amplifier to 

saturate and become overloaded. Some common mechanical causes of an overload in the sensor are severe 

pump cavitation, steam release, impacts from loose or reciprocating parts and even gearmesh.  One way to 

reduce clipping is to use a higher power supply voltage and ensure that the bias voltage is centered between 

supply voltage and ground voltage. However the bias voltage and power supply are rarely adjustable. For ex-

ample, if you are using an 18 volt power supply and a 12 volt bias, clipping will occur sooner than if you used a 

24 volt power supply.

Long cables in excess of 200 feet can also reduce the amplitude swing at high frequencies and may be a 

problem in some applications. The easiest solution is to use a lower sensitivity sensor. A sensor with 10 mV/g 

sensitivity will have a hundred times larger amplitude range than a similar 1 V/g sensor.

Ski-slope spectrum

Sensor overload may also produce a ski-slope spectrum. If the amplifier saturates, intermodulation distortion 

occurs. This causes low frequency noise, also referred to as washover distortion. Figures 6a shows a normal 

spectrum.  Figure 6b shows what can happen when the signal becomes overloaded due to excessive vibration.

Figure 6a: Normal operation

Figure 6b: Overload operation

Sometimes the ski-slope signals can be caused by 

the circuitry used to integrate acceleration signals to 

velocity or displacement.  Figure 7 shows integration 

noise due to analog integration of an acceleration 

signal.

Figure 7: Ski-slope noise caused by analog integration

Page 5

Summary of Contents for Wilcoxon TN14

Page 1: ...capacitor in the measurement equipment leaving the AC output signal Most vibration data collectors monitors and sensor power units contain an internal blocking capacitor for AC coupling If not includ...

Page 2: ...a true analog representation of the vibration the sensor is attempting to measure Measuring the BOV The constant current diode CCD limits the current supplied to the sensor It provides a constant cur...

Page 3: ...een integrated to velocity or displacement may also produce ski slopes for various reasons Cable routing faults can also be detected by analyzing the FFT Multiples of the line power frequency usually...

Page 4: ...dustrial sensors typically contain protection devices to prevent these types of failures Figure 4 BOV trend of a sensor exposed to long term excessive temperatures Erratic bias and time waveform The b...

Page 5: ...ply voltage and ensure that the bias voltage is centered between supply voltage and ground voltage However the bias voltage and power supply are rarely adjustable For ex ample if you are using an 18 v...

Page 6: ...cally coupled signals Using shielded twisted pair cable will also help minimize any magnetically coupled noise into the signal cable For example if a power cable is 440 volts and the vibration signals...

Page 7: ...am release air leak cavitation etc Repair steam leak dump Use less sensitive sensor Place rubber pad under sensor 10 0 14 0 V Stable Very high low frequency ski slope No high frequency signal Choppy D...

Reviews: