6.4 Removing a Module
1. Pull out the tray, disconnect the fibers and replace their dust caps.
2. Repeat the same procedure on the back of the module.
3. Reach underneath the module and the tray to locate finger holes. Using one or two fingers, push up on the
module and pull it outward.
4. Remove the module from the tray.
6.5 Configuring and Installing Patch Modules
1. On the cassette, lay the fiber jumper to be installed in the patch module shuttle (
Fig. 6-6
), placing each jumper
between a section of the shuttle.
NOTE:
Amphenol Network Solutions requires the use of G.657.A1 fiber and recommends using G.657.A2
bend insensitive 1.6 or 1.2 mm fiber with short boots to further protect the fiber, also LC with low-profile
triggers are recommended.
2. Repeat this step for remaining fiber jumpers to be installed.
3. Remove protective dust cap from the patch module adapter port for the fiber jumper being installed.
NOTE:
To protect fibers, work with one fiber jumper at a time. Only remove the dust cap for the fiber jumper
being installed.
4. Clean adapter port with oil-free canned compressed air to remove any dust that has accumulated.
5. Remove the protective cover from the fiber jumper by pulling it straight out.
6. Inspect the end of the fiber jumper for any dust or debris. If needed, clean the fiber with lint wipes and a
commercial solution formulated for cleaning fiber surfaces or a reagent-grade ethyl alcohol to remove
particles.
7. Use a second dry wipe to dry the fiber.
8. Inspect again to ensure fiber end is clean; repeat Steps 3-7 if needed.
NOTE:
After confirming the fiber jumper end is clean, do not wipe the fiber or allow it to touch anything before
installing it in the adapter.
9. Insert the clean, dry fiber into the adapter port.
10. Using the sticker kit that came with the module, label each port with the corresponding number
(Fig. 6-7)
.
11. Locate adapter designation number on the designation card located on the front door of the C2LINX chassis.
Record designation information.
Fig. 6-6: Installing fiber jumpers
Shuttle