nrg600BT08-M 

Amphenol Network Solutions 

All rights reserved. 12.05.19 145121-2 A0 

509.926.6000 – amphenol-ns.com 

Specifications

 

Inputs 

Voltage range, nominal voltage  -40V to -60V (Nominal -48 VDC) 
Max. input load rating 

600A per side at max. 

Short circuit withstand rating 

5000A (breakers/fuses); 450A GMT 

Nominal power loss at full load  Less than 75W per side @ 28,000W 

full load per side (600A x 48V) 

Percentage of full power 

dissipation at nominal voltage 

Less than 1% 

Max. input interrupt device 

750A 

Input terminal studs 

(with nuts, flat washers and 

spring washers) for dual-hole 

compression lugs 

• 

Two pair of 3/8 – 16 studs on 1 

in. centers per terminal [max. 

lug width of 1.94 in. (49.2 mm)] 

per pair 

• 

Torque nut (using 9/16 in. or 15 mm 

wrench) to 150 in.-lb (~17 N•m), 

max. 

Input wire size 

#1 AWG to 750 MCM 

Dual-Hole Outputs 

Max. output single-pole, long- 

delay circuit breaker (ea.) 

100A 

Max. output TPS or TLS 

125A 

Max. output load (ea.) - 

continuous 

100A 

Minimum short circuit 

interrupt rating 

5000A 

Output terminal studs (with 

KEPS, nuts and washers) 

for dual-hole compression 

lugs 

• 

1/4 - 20 studs on 5/8 in. centers 

[max. lug width of 0.680 in. 

(15.8 mm) for a BATT terminal 

and 

0.70 in. (17.7 mm) for a RETURN 

terminal]. 

• 

Torque bolts (using 7/16 in. or 12 

mm wrench) to 50 in.-lb (~5.5 

N•m), max. 

Output wire size 

#14 AWG minimum 

GMT Outputs 

Max. GMT output fuse (ea.) 

20A 

Max. GMT output load (ea.) - 

continuous 

14A 

Minimum short circuit interrupt 

rating 

450A 

GMT output terminals for 

compression lugs 

• 

10 removable, #6-32 panhead 

screws (max. lug width of 0.29 in. 

[7.4 mm]). 

• 

Torque to 6.3 in.lb (~0.7N•m), max. 

GMT output wire size 

#22 AWG to #12 AWG, depending on 

output fuse rating 

Dry Contact Alarms 

Alarm wire size 

#22 to #18 AWG 

Alarm terminals 

Wire wrap 

Relay contact ratings 

Dry Form-C contacts (1A @ 30 VDC, 

0.5A @ 60 VDC, 0.3A @ 125 VAC) 

Max. alarm power rating 

@24V: 72 mA (1.73W) 

@48V: 147 mA (7.06W) 

Grounding 

Earth GND terminal bolts 

(with washers) for dual-hole 

compression lug 

• 

Two pair of 1/4 - 20 threaded 

holes on 5/8 in. centers. 

• 

Torque bolts (using 7/16 in. or 12 

mm wrench) to 50 in.-lb (5.5 N•m), 

max. 

Ground wire size 

#2 AWG recommended 

Voltage Sensor 

Sensor accuracy 

0 to -19.99V: ±0.3V 

-20V to -60V: ±0.1V 

Voltage measurement range 

0 to -60 VDC 

Feed voltage detection 

0 to -19.99V: Alarm 

-20V to -60V: Normal 

NOTE: 

• 

Voltage measurement may be slightly different than at input 

terminal blocks due to the voltage drop within the panel. 

• 

Sensors are factory calibrated and do not require user adjustment. 

Communication 

nrgNET sensor and alarm 

card power 
(via nrgNET cabling 

connection to an 

nrgCONTROL-BT controller) 

-48 VDC nominal 

*NOTE:

 The nrg600BT08-M chassis 

MUST BE connected to an 

nrgCONTROL-BT controller via 

nrgNET cabling for LED Alarm 

Indicators to function 

nrgNET data communication 

RS-485 

nrgNET connector 

Removable 5-pin connector with 

screw down terminals 

nrgNET connector functions 

nrgNET IN from the nrgCONTROL or 

nrgSMART Panel, nrgNET OUT to next 

inline nrgSMART panel 

LED Alarm Indicators  
(requires nrgNET & controller 

for power) 

A/B bus power 
A/B fuse alarms 
nrgNET Comms active 

Supported protocols 

Proprietary nrgNET used to 

communi- cate between panels and 

controller 

Fit and Finish 

Material 

14-gauge steel 

Color 

Pewter grey powder coat 

Mechanical 

Dimensions (L x W x H): 

12” x 17.25” x 7” 

Rack space 

4RU 

Environmental 

Operating temperature 

-5° to +44°C 

Humidity 

0 to 90%, non-condensing 

Weight (approximate) 

Installed 

47 lb (21.3kg) 

Shipping 

49.1lb (22.3kg) 

Compliance 

 

 

UL, NEBS level 3 

Warranty 

 

 

Standard 1-year warranty on all parts. 

 

The warranty is extended through the addition of the annual 

maintenance and support contract (nrgSMART-APSC) 

 

Summary of Contents for nrg600BT08-M

Page 1: ...nrg600BT08 M Power 600A Load Center with nrgSMARTTM Remote Monitoring Installation Guide...

Page 2: ...d communications markets We design manufacture and distribute products for customers who need an end to end solution for network connectivity fiber power distribution and rack management We collaborat...

Page 3: ...terminals for inputs outputs ground and alarms are on the rear of the panel All terminals are covered by a single full width transparent terminal cover Inputs are studs for dual hole lugs Ground term...

Page 4: ...3 8 studs on 1 centers A Feed Inputs 3 8 studs on 1 centers B Feed Bullet Load Terminal 1 4 studs on 5 8 centers B Feed GMT Load Terminal 6 Single Screw Temperature Probe Input Temperature Probe Inpu...

Page 5: ...s Wire wrap Relay contact ratings Dry Form C contacts 1A 30 VDC 0 5A 60 VDC 0 3A 125 VAC Max alarm power rating 24V 72 mA 1 73W 48V 147 mA 7 06W Grounding Earth GND terminal bolts with washers for dua...

Page 6: ...list Please report any defective or missing parts to Amphenol Network Solutions at getinfo amphenol ns com or call 509 926 6000 Amphenol Network Solutions is not liable for transit damaged If the prod...

Page 7: ...PDU or battery 12 Insulate lug barrels with UL94 V 0 rated heat shrink tubing 13 Clean terminals and lugs with nonabrasive nonmetallic pad 14 If required lightly coat antioxidant on lugs and input BA...

Page 8: ...LED In this mode the power and fuse LEDs are used for diagnostics and do not represent the power and fuse status A blinking green PWR B LED in conjunction with the yellow PWR A LED indicates the firmw...

Page 9: ...as required by NEC b Clean the panel terminals and lug if applicable witha nonabrasive nonmetallic cleaning pad c If required lightly coat antioxidant on lug wire and output BATT and RETURN terminals...

Page 10: ...t the applicable FUSE Alarm LED turns red Also check the FUSE alarm terminals on the rear of the panel Expect an open circuit between Terminals C and NC Expect continuity 0 between Terminals C and NO...

Page 11: ...50MCM AWG T B 54209 54210 54211 54216 54218 Panduit LCD1 0 38D X LCD2 0 38D X LCD3 0 38D X LCD400 38D 6 LCD500 38D 6 LCDN750 38D 6 Burndy YA322TC38 YA342TC38 YA392NT38 The following table describes th...

Page 12: ...ble Pole 125A 134634 2A 119103 150A 134635 3A 124210 175A 135921 5A 117852 Triple Pole 200A 134636 10A 116669 225A 134637 15A 115999 250A 134638 20A 116670 25A 117402 30A 116671 40A 116672 50A 116673...

Page 13: ...moved with the nrgNET power still connected Hot Swapping to the panel The replacement part number for the nrg600BT08 M card is 306308 WARNING Handle the alarm card with care The alarm card is ESD sens...

Page 14: ...14 nrg600BT08 M Amphenol Network Solutions All rights reserved 12 05 19 145121 2 A0 509 926 6000 amphenol ns com nrgNET Connectivity...

Page 15: ...926 6000 amphenol ns com nrgNET Pin Outs Table 6 nrgNET Pinouts Pin Number Label Wire Pin 1 COM White 22 AWG Pin 2 COM Blue 22 AWG Pin 3 S Drain Wire 24 AWG Pin 4 PWR Black 18 AWG Pin 5 PWR Red 18 AWG...

Page 16: ...16 nrg600BT08 M Amphenol Network Solutions All rights reserved 12 05 19 145121 2 A0 509 926 6000 amphenol ns com Front View Top View Rear View Side View...

Page 17: ...USBAR ADAPTER 3 POLE 600CB08 3 pole bridge nrg600CB08 SGL KIT nrgSMART ACC A B BUSS BAR BRIDGE TO SINGLE FEED nrgSMART Circuit Modules BT nrgSMART MOD BT PASS THROUGH 48V nrgBT nrgSMART MOD BT CURRENT...

Page 18: ...interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at hi...

Page 19: ...19 nrg600BT08 M Amphenol Network Solutions All rights reserved 12 05 19 145121 2 A0 509 926 6000 amphenol ns com This page intentionally left blank...

Reviews: