nrg600BT08-M 

Amphenol Network Solutions 

All rights reserved. 12.05.19 145121-2 A0 

509.926.6000 – amphenol-ns.com 

 

Accessories & Alarm Card 

 

The following lists optional and replacement items for the panel. 

 

WARNING! Use only UL-listed fuses or UL-recognized component secondary protection devices. 

 

Input & GND Lugs 

The following table describes the available input lugs for stranded copper conductors with straight dual-hole lugs for 3/8-in. studs on 1-in. centers. 

 

Table 2 – Input Lugs 

 

Source 

#1/0 AWG 

#2/0 AWG 

#3/0 AWG 

400MCM AWG 

500MCM AWG 

750MCM AWG 

T & B 

54209 

54210 

54211 

54216 

54218 

 

Panduit 

LCD1/0-38D-X 

LCD2/0-38D-X 

LCD3/0-38D-X 

LCD400-38D-6 

LCD500-38D-6 

LCDN750-38D-6 

Burndy 

 

 

 

YA322TC38 

YA342TC38 

YA392NT38 

 

 

 

 

The following table describes the available ground lugs for stranded copper conductors with 90° dual-hole lugs for 1/4-20 bolts on 5/8" centers. 

 

 

Table 3 – Ground Lugs 

 

Source 

#2 AWG 

#4 AWG 

#6 AWG 

#8 AWG 

T&B 

54207 

54206 

54205 

 

Panduit 

LCDN2-14A-Q 

LCD4-14A-L 

LCD6-14A-L 

LCD8-14A-L 

Burndy 

YA2CL2NT14 

YA4CL2TC14 

YA6CL2TC14 

YA8C2TC14 

 

 

 

 

Table 4 – Single-Hole Ring Lug 

 

 

#22-18 AWG 

#22-16 AWG 

#16-14 AWG 

#12-10 AWG 

AMP 

51863 

51863 

320619 

329697 

Panduit 

PN18-6R-M 

PV14-6RNB-3K 

Burndy 

YAE18N-21BOX 

YAE14N-43BOX 

 

(Insulated Barrels) with Part Numbers vs Output Wire Size (For #6 Panhead Screws) 

Summary of Contents for nrg600BT08-M

Page 1: ...nrg600BT08 M Power 600A Load Center with nrgSMARTTM Remote Monitoring Installation Guide...

Page 2: ...d communications markets We design manufacture and distribute products for customers who need an end to end solution for network connectivity fiber power distribution and rack management We collaborat...

Page 3: ...terminals for inputs outputs ground and alarms are on the rear of the panel All terminals are covered by a single full width transparent terminal cover Inputs are studs for dual hole lugs Ground term...

Page 4: ...3 8 studs on 1 centers A Feed Inputs 3 8 studs on 1 centers B Feed Bullet Load Terminal 1 4 studs on 5 8 centers B Feed GMT Load Terminal 6 Single Screw Temperature Probe Input Temperature Probe Inpu...

Page 5: ...s Wire wrap Relay contact ratings Dry Form C contacts 1A 30 VDC 0 5A 60 VDC 0 3A 125 VAC Max alarm power rating 24V 72 mA 1 73W 48V 147 mA 7 06W Grounding Earth GND terminal bolts with washers for dua...

Page 6: ...list Please report any defective or missing parts to Amphenol Network Solutions at getinfo amphenol ns com or call 509 926 6000 Amphenol Network Solutions is not liable for transit damaged If the prod...

Page 7: ...PDU or battery 12 Insulate lug barrels with UL94 V 0 rated heat shrink tubing 13 Clean terminals and lugs with nonabrasive nonmetallic pad 14 If required lightly coat antioxidant on lugs and input BA...

Page 8: ...LED In this mode the power and fuse LEDs are used for diagnostics and do not represent the power and fuse status A blinking green PWR B LED in conjunction with the yellow PWR A LED indicates the firmw...

Page 9: ...as required by NEC b Clean the panel terminals and lug if applicable witha nonabrasive nonmetallic cleaning pad c If required lightly coat antioxidant on lug wire and output BATT and RETURN terminals...

Page 10: ...t the applicable FUSE Alarm LED turns red Also check the FUSE alarm terminals on the rear of the panel Expect an open circuit between Terminals C and NC Expect continuity 0 between Terminals C and NO...

Page 11: ...50MCM AWG T B 54209 54210 54211 54216 54218 Panduit LCD1 0 38D X LCD2 0 38D X LCD3 0 38D X LCD400 38D 6 LCD500 38D 6 LCDN750 38D 6 Burndy YA322TC38 YA342TC38 YA392NT38 The following table describes th...

Page 12: ...ble Pole 125A 134634 2A 119103 150A 134635 3A 124210 175A 135921 5A 117852 Triple Pole 200A 134636 10A 116669 225A 134637 15A 115999 250A 134638 20A 116670 25A 117402 30A 116671 40A 116672 50A 116673...

Page 13: ...moved with the nrgNET power still connected Hot Swapping to the panel The replacement part number for the nrg600BT08 M card is 306308 WARNING Handle the alarm card with care The alarm card is ESD sens...

Page 14: ...14 nrg600BT08 M Amphenol Network Solutions All rights reserved 12 05 19 145121 2 A0 509 926 6000 amphenol ns com nrgNET Connectivity...

Page 15: ...926 6000 amphenol ns com nrgNET Pin Outs Table 6 nrgNET Pinouts Pin Number Label Wire Pin 1 COM White 22 AWG Pin 2 COM Blue 22 AWG Pin 3 S Drain Wire 24 AWG Pin 4 PWR Black 18 AWG Pin 5 PWR Red 18 AWG...

Page 16: ...16 nrg600BT08 M Amphenol Network Solutions All rights reserved 12 05 19 145121 2 A0 509 926 6000 amphenol ns com Front View Top View Rear View Side View...

Page 17: ...USBAR ADAPTER 3 POLE 600CB08 3 pole bridge nrg600CB08 SGL KIT nrgSMART ACC A B BUSS BAR BRIDGE TO SINGLE FEED nrgSMART Circuit Modules BT nrgSMART MOD BT PASS THROUGH 48V nrgBT nrgSMART MOD BT CURRENT...

Page 18: ...interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at hi...

Page 19: ...19 nrg600BT08 M Amphenol Network Solutions All rights reserved 12 05 19 145121 2 A0 509 926 6000 amphenol ns com This page intentionally left blank...

Reviews: