background image

POWER LED not illuminated

:

Check that the power (

O

 / 

I

) switch is toggled to the ON (

I

) position.

A 20mm fuse is incorporated in the AC POWER socket. It is necessary to 
remove the power cord before extracting the fuse holder. Test the continuity 
of the fuse using a multimeter. A spare fuse is provided in the fuse holder.

Any replacement fuse 

must

 be of the same fuse rating and type as 

printed on the rear panel of the unit.

POWER LED flashing continuously

Amplifier has failed self test and is in safe mode. No signal will be fed into 
the loop. Switch the unit OFF, remove all connections except the loop and 
power connections, turn all front panel controls to minimum and switch back 
ON. If the problem persists, contact Ampetronic for advice.

COMPRESSION LEDs not illuminating

Check input connections.

Ensure that the appropriate front panel control (Mic / Line) is turned up.

Check that there is sufficient signal level for the required input.

CURRENT LEDs not illuminating

Check that the COMPRESSION LEDs are illuminating.

Check that the LOOP CURRENT control is turned up sufficiently.

Check that the LOOP ERROR, or OVERHEAT LEDs are not illuminated.

Ensure the POWER LED is illuminated and not flashing.

Remove any connection to the SLAVE I/O socket.

Check that the loop cable is connected, terminated correctly and inserted 
into the LOOP OUTPUT socket.

Check the loop cable is not open circuit, short circuit, or connected to earth 
(see Instability or high frequency noise section of Troubleshooting).

Note: You can listen to the actual loop signal by using a pair of headphones 
plugged into the loop monitor socket.

OVERLOAD LED illuminated

Indicates that too much current is being delivered into the loop.

Check that the COMPRESSION LEDs are illuminating.

Remove any connection to the SLAVE I/O socket.

Turn the LOOP CURRENT control down to avoid running too much current 
into the loop.

TROUBLESHOOTING

 

Check the loop cable is not open circuit, short circuit, or connected to earth 
(see Instability or high frequency noise section of 

Troubleshooting

).

OVERHEAT LED illuminated:

Indicates that the internal heatsink is too hot. Loop current is not delivered.

Ensure that the unit is installed in a location with sufficient ventilation.

Check the loop cable is not open circuit, short circuit, or connected to earth 
(see Instability or high frequency noise section of Troubleshooting).

LOOP ERROR LED illuminated:

Indicates that the loop cable connected to the unit is outside specification.

Check that the loop cable is connected, terminated correctly and inserted 
into the LOOP OUTPUT socket. Ensure the DC resistance is acceptable.

Low magnetic field strength:

Due to insufficient LOOP CURRENT or excessive metal loss.

May require a special loop design to achieve acceptable performance, 
contact Ampetronic for advice.

Instability or high frequency noise

1) It is possible for the loop cable to become grounded under fault 
conditions, resulting in instability which may sound like high frequency 
noise, buzz or whistling. The results of this type of fault are unpredictable 
and may appear as any combination of the front panel indication errors.

This fault is easy to determine: simply unplug the loop cable from the 
amplifier and test with a resistance meter between either of the loop wires 
and a good earth point such as a metal radiator. There should be an 
infinitely high reading i.e. no connection at all. Any reading indicates a 
failure of the loop cable insulation and you will need to either repair or 
replace the loop cable.

2)

 

Instability can be caused by using poor quality signal cables, long 

unbalanced (2-wire) signal runs to the inputs, or by running input cables in 
close proximity with the loop wire over any appreciable distance. Loop 
amplifiers are capable of delivering high currents at audio frequencies. If 
the loop cable is run close to sensitive signal cables it may be possible to 
induce a signal back into the input of the amplifier causing feedback. Cable 
runs and loop wires should be kept well apart from each other. To avoid 
interference a proximity of 300mm should only be run for a few meters. 
Always used balanced (3-wire) circuits where possible. 

Summary of Contents for ILD122

Page 1: ...ord or plug is damaged liquid has been spilled or objects have fallen into the apparatus the apparatus has been exposed to any rain or moisture does not operate normally or has been dropped 9 WARNING...

Page 2: ...eld strength meter 10 Adjust METAL LOSS CORRECTION to achieve a flat frequency response All you need is a power source a signal source and a loop See Designing Induction Loops handbook or contact Ampe...

Page 3: ...p cable METAL LOSS CORRECTION Screwdriver adjustable control which compensates for the frequency dependent effects of metal SLAVE I O Post compressor signal for use with ancillaries 15V 150mA DC OUTPU...

Page 4: ...CONNECTOR Signal TIP SOURCE TO ILD122 SLEEVE RING LINE INPUT Connection of 3 pole plug Use Twin screened cable Must be 3m or less Unbalanced Balanced TIP RECORDING DEVICE TO ILD122 SLAVE I O SLEEVE RI...

Page 5: ...including a wire stripper and a small flat bladed screwdriver An ILR3 loop receiver or a magnetic field strength meter is vital to check that the loop system is providing the desired level of perform...

Page 6: ...han 20m in length Total resistance of loop and feed must be between 0 2W and 1 8W at DC The Designing Induction Loops handbook contains more details on loop and feed cables The correct design and posi...

Page 7: ...Metal losses tend to increase with frequency and may require the adjustment of the METAL LOSS CORRECTION As a result of this analysis adjust the LOOP CURRENT and set the METAL LOSS CORRECTION on the...

Page 8: ...Mic Line is turned up Check that there is sufficient signal level for the required input CURRENT LEDs not illuminating Check that the COMPRESSION LEDs are illuminating Check that the LOOP CURRENT cont...

Page 9: ...in instability which may sound like high frequency noise buzz or whistling The results of this type of fault are unpredictable and may appear as any combination of the front panel indication errors T...

Page 10: ...receiver such as an ILR3 If the interference is still present with the loop system switched off then you need to locate and eliminate the source of interference before switching the loop system back o...

Page 11: ...Vpk at 7 0Apk output Input Impedance 200 600W Sensitivity 70dBu 245uV for full RMS 15V 150mA DC Output output 3 pin power Mini DIN socket Overload 5dBu 436mV RMS Regulated DC output for powering Ampet...

Page 12: ...en it is installed Manufacturer Ampetronic Ltd Northern Road Newark Nottinghamshire NG24 2ET United Kingdom Declares that the product Description Induction Loop Driver Type name ILD122 Conforms to the...

Reviews: