APPENDIX D: ELV-PRO Modbus TCP
D1 Modbus Commands
The following Modbus commands are supported:
Table 10: Modbus Commands
Modbus CMD
Comment
03
Read Holding Registers
06
Store Single Register
Valid read registers are in the range from 4 to 109. An attempt to read a register outside this range will
result in an exception scan. Supported Modbus exception responses are:
Table 11: Modbus Exception
Modbus Exception
Comment
01
Illegal Function
02
Illegal Data Address
03
Illegal Data Value
D2 Modbus Status
Table 12: Modbus Status
Status
Comment
Address
The Modbus slave address the ELV-PRO is set
to
Read
A solid block when a READ command is
received
Wrt
A solid block when a WRITE command is
received
Exc
A solid block when an unsupported Modbus
command is received
CRC
A solid block when a checksum error is
detected
Par
A solid block when a parity error is detected
NE
A solid block when noise is detected
FE
A solid block when a framing error is detected