4.4.1 Power Supply (Plug 3)
The ELV-PRO requires a regulated 24VDC power supply. There are two input supply connections for
both the 0V and +24VDC inputs. These connections are internally connected. Terminals P3_1 & P3_2
are the positive supply inputs. Terminals P3_3 & P3_4 are the negative supply inputs.
Figure 4-4: Electrical Connections
– ELV-PRO Power Supply (Plug 3)
NOTE
There are two internally connected input supply terminations for each
input. The additional connection is to allow for daisy chaining to other
devices.
4.4.2 Trip Reset and Digital Inputs (Plug 2 & Plug 4)
The trip reset and digital inputs are split across two plugs; Plug 2 and Plug 4 (see Figure 4-5). Plug 2
(right) is a dedicated digital input and Trip Reset 24V supply. All terminals of plug 2 are internally
connected. Plug 4 (left) is a dedicated input plug; terminals P4_1 - P4_5 are assignable digital inputs,
with terminal P4_6 the Reset input. The Trip Reset Input allows the ELV-PRO to be reset remotely.
Figure 4-5: Electrical Connections
– Trip Resent and Digital Inputs (Plugs 2 & 4)
ELV-PRO
P3_1
24VDC
Control Supply
Plug 3
+24VDC
0V
P3_2
P3_3
P3_4
ELV-PRO
DI1
DI2
DI3
DI4
DI5
RST
ELV-PRO
P4_6
P4_5
P4_4
P4_3
P4_2
P4_1
P2_6
P2_5
P2_4
P2_3
P2_2
P2_1
+24VDC
Plug 4
Plug 2
RESET P/B